Toshiba MMY-MUP0801HT8P-TR Service Manual page 148

Air conditioner multi type, super modular multi system-u smms-u, outdoor
Table of Contents

Advertisement

Note 1: Criteria for the difference between suction and discharge temperatures
(1) Cooling operation
After operating for a minimum of 30 minutes in "COOL" mode, if the T dry bulb temperature difference
between suction and discharge air of the indoor unit is 8°C or more, it is normal.
(2) Heating operation
After operating for a minimum of 30 minutes in "HEAT" mode, if the T dry bulb temperature difference
between suction and discharge air of the indoor unit is 15°C or more, it is normal.
* If demand from the indoor unit on the outdoor unit is low because the difference between the temperature
set by the remote controller and the temperature of the room is small, then the T temperature difference is
small.
* Consider that T temperature difference may diminish in cases of a system in which the connected indoor
unit capacity exceeds the outdoor unit capacity, the pipe length is long, or a large difference exists among
outdoor units.
Note 2: Criteria for operating power current
The table below shows the maximum current for each outdoor unit. Under standard conditions, operating
current is about 80% of the value shown in the table below.
Model
MMY-MUP
Current value
Model
MMY-MUP
Current value
Note 3: Criteria for cycle status
(1) These data are based on operating a 4-way Air Discharge Cassette type air conditioner of 100%
connection with standard piping length.
Data may vary depending on temperature conditions, installed pipe length, and room shape combinations,
or indoor unit connection capacity.
For pressure criteria in different temperature conditions, refer to (2).
Pressure
Outdoor
Operating
(MPa)
Unit
Mode
MMY-MUP
Pd
Ps
Cooling
3.0 1.0
0801*
Heating
2.4 0.7
Cooling
3.1 1.0
1001*
Heating
2.8 0.7
Cooling
3.4 1.1
1201*
Heating
2.5 0.7
Cooling
3.7 1.1
1401*
Heating
2.4 0.7
Cooling
3.2 1.0
1601*
Heating
2.5 0.6
Cooling
3.4 1.0
1801*
Heating
2.5 0.6
Cooling
3.3 0.9
2001*
Heating
2.5 0.6
Cooling
3.5 1.0
2201*
Heating
2.7
0.6
Cooling
3.7 1.0
2401*
Heating
2.6 0.6
* This compressor is driven with a 6-pole motor. The value of the compressor frequency (rps) measured with a
clamp meter at the compressor lead line is three times the rotation count (rps) of the compressor.
* Each compressor may have a different frequency as a measure against resonance.
* The temperature of the indoor heat exchanger (TC) indicates TCJ sensor temperature when cooling, and
TC2 sensor temperature when heating, respectively.
(2) Criteria for operating pressure
Pressure
Operating
(MPa)
Mode
Pd
PS
Cooling
2.0 ~ 3.3
0.5 ~ 0.9
Heating
2.5 ~ 3.3
0.5 ~ 0.7
* Criteria after 14 minutes or more has passed since operating started
0801*
1001*
(A)
15.4
20.5
1801*
2001*
(A)
34
36
Pipe Surface Temperature
(ºC)
Indoor Heat Outdoor Heat
Discharge Suction
Exchanger
Exchanger
TD1
TS1
TC2
15
79
21
67
2
25
82
21
15
79
2
23
86
21
15
75
1
25
91
20
16
73
1
26
85
19
15
71
-1
27
90
19
14
72
-2
27
92
20
14
79
0
25
94
27
15
82
-1
25
98
21
15
81
-1
24
Temperature
ºC
Indoor
Outdoor
18 ~ 32
25 ~ 35
15 ~ 32
5 ~ 35
1601*
1201*
1401*
30.5
24.5
27.5
2201*
2401*
51
54
Compressor Rotation
Liquid
Compressor 1 Compressor 2
Temperature
TE1
TL3
Cmp. 1
39
26
50
57
1
21
40
26
56
0
17
63
40
29
65
0
16
75
41
33
77
-1
22
83
43
28
65
1
17
68
42
28
70
2
22
77
43
31
77
0
1
82
42
29
71
0
-4
79
43
30
78
0
20
79
- 148 -
Air Temperature
(rps)
(DB/WB)(ºC)
Indoor
Fan
Outdoor
Cmp. 2
TO
35
High
7
High
High
35
High
7
High
35
High
7
High
35
High
7
High
35
High
7
High
35
High
7
High
35
High
7
70
High
35
77
High
7
77
High
35
77
High
7
Indoor
TA
27
20
27
20
27
20
28
20
27
20
27
20
27
20
27
20
27
20