Toshiba MMY-MUP0801HT8P-TR Service Manual page 60

Air conditioner multi type, super modular multi system-u smms-u, outdoor
Table of Contents

Advertisement

Item
Description of operation, numerical data, and other information
(1) Current, power release value control
12. Inverter
P.C.board
The purpose of this control is to prevent high pressure rise and overheating of electric
parts by reducing the compressor speed when the maximum current and maximum
control for
compressor
power value set for each model are exceeded.
The maximum current and power value for each horsepower
of each model are as follows
HP
24*
22*
20
18
16
14
12
10
8
*2 For comp models, it is the maximum value per comp.
Even when the TH sensor temperature ≥ 81°C, the compressor speed is reduced, and
when the TH sensor temperature < 73°C continues, the rotation speed increase is
permitted.
(2) Heat sink overheat abnormality
Stop the compressor operation when the TH sensor temperature exceeds 93°C.
When the above is stopped, the abnormal count is set to 1, and it restarts after 2
minutes and 30 seconds.
If you continue the operation for 10 minutes or more after restarting, the trouble count
will be cleared
A trouble is confirmed with a trouble count of "4".
(3) High pressure SW control
Inverter compressor stops driving the compressor when the high pressure SW is
operating.
When the above is stopped, the abnormal count is set to 1, and it restarts after 2
minutes and 30 seconds.
If you continue the operation for 10 minutes or more after restarting, the trouble count
will be cleared.
The trouble count becomes "4" and the trouble is confirmed.
The above display is "P04".
Maximum current
Maximum power
27.00A
17.21kW
25.50A
16.25kW
36.00A
22.94kW
34.00A
21.67kW
30.50A
19.44kW
27.50A
17.52kW
24.50A
15.61kW
20.50A
13.06kW
15.40A
9.81kW
- 60 -