Manual address setup from the remote controller
With indoor wiring work completed and outdoor wiring work not done—in cases where indoor unit addresses are
decided in advance from the wired remote controller, or in cases where addresses are change after address setup.
(Wiring example for 2 refrigerant lines)
Line 1
Outdoor
Indoor 1
Indoor 2 Indoor 3
Remote
controller
(Remote controller group control)
Line address
1
1
Indoor address
1
2
Group
1
2
address
Header
Follower Follower
In the above example, where remote controllers are not
yet wired, set the address manually after individually
connecting the wired remote controller.
(Wiring during manual address setup)
Line 1
Outdoor
Indoor 1 Indoor 2 Indoor 3
Remote
Remote
Remote
controller
controller
controller
After address setup, return to the original
wiring over remote controllers.
Group address
Individual: 0000
In cases of
Header unit: 0001
remote controller
Follower unit: 0002
group control
Set
data
TEMP.
4
TIMER SET
7
TIME
10
FILTER
RESET
TEST
SET
CL
SWING/FIX
13
5, 8, 11, 14
6, 9, 12, 15
16
3
<RBC-AMT*>
1
Line 2
Outdoor
2
3
Indoor 1 Indoor 2
1
2
2
3
1
2
4
2
2
2
Follower Follower
5
Line 2
6
Outdoor
7
Indoor 1 Indoor 2
8
Remote
Remote
controller
controller
9
10
11
12
13
ON / OFF
DN code
(CODE No.)
14
FAN
MODE
SAVE
VENT
15
UNIT LOUVER
16
17
Arrange one indoor unit and one remote
controller set to 1 by 1.
Turn on the power.
Push the
+
+
seconds or more.
LCD begins blinking.
(Refrigerant line address)
Using the
buttons, set the DN code to 12.
Using the
buttons, set up the line address
(match it with the line address on the interface
P.C. board of the header unit on the same
refrigerant line).
Push the
button (OK when the display goes on).
(Indoor address)
Using the
buttons, set the DN code to 13.
Using the
buttons, set up the indoor address.
(0001~0064)
Push the
button (OK when the display goes on).
(Group address)
Using the
buttons, set the DN code to 14.
Using the
buttons, set Individual = 0000,
Header unit = 0001, Follower unit = 0002.
Push the
button (OK when the display goes on).
(Central control address)
Using the
buttons, set DN code to 03.
Using the
buttons, set up the central
control address. (0001~0064)
Push
button. (OK when display goes on).
Push the
button.
Setup is finished ("Setting up" blinks; when "Setting up"
goes off, operation is possible).
Return to the original wiring over remote
controllers.