Technical data

Type
Power supply
Rated power
Stand-by operating
Output voltage
Ripple
Output rated current
Number of lines / groups * 2 / 3
Fire detector per line
SHEV button per Line
Current per group **
Mode of operation
- Monitoring
- Alarm / ventilation
Housing
Colour
Ingress protection
Protection class
Temperature range
Dimensions WxHxD
* D+H Highspeed (HS) drives will be supported.
** The total current of the control panel must not be exceeded.

24 V - Emergency supply

Emergency power supply for 72 hours.
Use VdS approved storage batteries only!
2x 12V / 7,0 Ah ±0,3Ah (Type 3)
With connection of D+H alarm devices:
2x 12V / 12 Ah ±0,3Ah (Type 4)
Battery control - TID
T Temperature-guided charging of accumulator
I Impedance measuring
Internal resistance of accumulator will be
measured cyclically. For example, if a total
discharged accumulator is connected to the
control panel = malfunction (LED on PCB)
D Discharge control
In case of power failure and total discharge of
accumulator, the control panel will switch off.
In this case, smoke vent is no longer ensured.
In this case a malfunction will be no more
indicated either.
99.823.21 3.2/01/15
RZN 4416-M
230 V AC, 50 Hz
500 VA
13,6 W
24 V DC (21,6 - 28,5 V)
2 Vss, load-dependent
16 A
max. 14 pcs.
max. 8 pcs.
max. 8 A
continuous duty
Short-time duty (30 % DC)
Steel sheet
light grey
IP 54
I
-5 ... +40 °C
500 x 500 x 210 mm
2x 12 V

Pictogram explanation

SHEV alarm
Malfunction
Control panel O.K.
OK
D+H window drive
Mains existing
Vent button function "OPEN"
Smoke-/ vent button function "CLOSE"
Charging voltage regulator
Ground short
20
40
OPEN running time limitation
sec
2
60
15
30
ventilation time limitation
min
2
45
English