Content
Motherboard / General Plug-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Supply plug-in card VE 520 / VE 530 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Line plug-in card LE 513 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Group plug-in card GE 628 (-L) V2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
Servo plug-in card SE 622 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11
Weather plug-in card WE 516. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Window-lock plug-in cardAE 525-AandAE 526-DG. . . . . . . . . . . . . . . . . . . 13
Trouble shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Examination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Important Regulations
Regulations for Hazard detection systems VDE 0833, Guidelines for
electrical systems VdS 2221, VDE 0100, DIN 18232 for smoke and heat
ventilation systems, regulations from the local fire-authorities and from
energy supply company, for mains supply connection must be observed.
Maintenance
Once a year by a specialist company authorised by the equipment
manufacturer.
-
Renew test badge.
-
Update logbook.
The respective current D+H maintenance instructions should be followed.
A D+H authorised company has been specially trained by D+H for carrying
out this maintenance competently and will be automatically provided with
the latest maintenance instructions.
Following tests must be carried out during maintenance:
-
External examination and inspection of system components
-
Measuring of insulation resistances
-
Checking of all relevant power supply units.
-
Functional testing of connected system components.
-
Logging the competent execution of maintenance and identification
thereof in accordance with directions.
Guarantee
You will get
2 years
guarantee for all D+H products from date of verified
handing over of the system up to maximal 3 years after date of delivery,
when mounting and starting has been carried out by a D+H authorized
distributor
.
D+H guarantee is expired, with connection of D+H components with
external systems or with mixing of
manufacturers.
24 V - Emergency Supply
Emergency power supply for 72 hours.
Use only VdS approved accumulators.
RZN 4308-E
:
2 x accumulator type 3 (12V, 7,0Ah ± 15%)
RZN 4316-E
:
2 x accumulator type 4 (12V, 12Ah ± 15%)
RZN 4332-E
:
2 x accumulator type 5 (12V, 18Ah ± 15%)
RZN 4364-E
:
2 x accumulator type 6 (12V, 26Ah ± 15%)
Technical Data
Type of control panel
RZN 4308-E
Rated voltage
230 VAC, 50Hz
Rated power
240 VA
Stand-by operating
ca. 10,4 W
Interfering emission
DIN EN 55011; DIN EN 50081-2
Resistance to jamming
DIN EN 61000-4 -2, -3, -4
Protection class
I
Temperature range
-5 bis +40 °C
Ingress protection
IP54
Class of rating
- Monitoring
Continous duty
- Alarm / ventilation
short-time duty
Output voltage
24VDC / residual ripple
Safe output
- running current of drives
- rated current of drives
Housing
sheet steel
colour of housing
RAL 7035; light grey
Housing dimensions
...-E6
...-E9
...-E14
2/16
RZN 43xx-E
D+H products with parts of other
RZN 4316-E
230 VAC, 50Hz
500 VA
ca. 11 W
48%
6,4 A
8 A
500 x 500 x 210
...-E6
600 x 600 x 210
...-E9
600 x 600 x 210
...-E14
Pictograph Explanation
Smoke and heat vent alarm
OK
Control panel O.K.
M
Fuse drive
Power supply
Vent button function "OPEN"
Vent/ smoke vent function "CLOSE"
Fault
Battery fault
Charging voltage controller
Window-lock group / fuse
Smoke-vent button / fuse
Smoke detector / fuse
Ground fault
Check pins ground fault
Regulator for wind-force switchpoint
Regulator for signal storage time
Stroke-instantaneous value in per cent
Hysteresis
2
15
min
Regulator for Ventilation time
45
30
2
20
sec
Regulator for OPEN running time
60
40
Automatic temperature control
Automatic weather control activated
Signal "rain"
Signal "wind-force switchpoint"
AUTO
Weather automatic switched on
RZN 4332-E
230 VAC, 50Hz
1000 VA
ca. 16,2 W
12,8 A
25,6 A
16 A
32 A
500 x 500 x 210
...-E6
600 x 600 x 210
600 x 600 x 210
...-E9
600 x 600 x 210
600 x 600 x 210
...-E14
600 x 800 x 250
RZN 4364-E
230 VAC, 50Hz
2000 VA
ca. 26 W
51,2 A
64 A
...-E12 800 x 1000 x 300
...-E15 800 x 1000 x 300
...-E20 800 x 1000 x 300
99.821.70 3.5/01/12