Operation - Day-to-day ventilation
Ventilation button or SHEV button with ventilation function RT 45-LT required.
Open:
ST OP
SMOKE VENT
OK
Operation - Weather automatic
Only if wind detector or rain detector available.
Upon triggering of the corresponding sensor, the
group of the control panel is closed.
If alarm is released by a smoke and heat vent
system, the system will open also in case of wind
and rain.
Do not ventilate via smoke vent button,
because otherwise there would be a danger of
damage by wind or water.
The weather automatic can be switched-off via an
optional automatic switch, if gap ventilation is
required in case of bad weather.
Gap ventilation is not possible in case of bad
weather, if no automatic switch available.
If the weather automatic is switched on , the
system will automatically
close in case of wind or rain.
The system will not
automatically open again,
if wind or rain has stopped.
Opening of the system for
ventilation via vent button.
99.823.21 3.2/01/15
Close:
ST OP
SMOKE VENT
OK
Automatic
on/off
LT 84-U-W
English
Stop:
Operation - AdComNet
In case of AdComNet operation (S6.4 = ON) the
ventilation control and alarm release can be
carried out by the local connected line and group
inputs, as well as via corresponding links in the
AdComNet Configurator.The alarm and fault
indicators distinguish between a local message
and a message inside a bus link:
Malfunction LED on the line:
1 Line deactivated: LED flashes
2 local fault: LED lights continuous
3 BUS fault: LED flashes
4 Everything OK: LED OFF
Malfunction LED on the group:
1 local fault: LED lights continuous
2 BUS fault: LED flashes
3 Everything OK: LED OFF
Alarm LED on the line:
1 local alarm: LED lights continuous
2 BUS alarm: LED flashes
3 No alarm: LED OFF
ST OP
SMOKE VENT
OK