AXIS A1214 Network Door Controller Kit
Specifications
UL: The connector has not been evaluated by UL for burglar or fire alarm use.
Function
DC ground
TAMPER
Function
DC ground
ALARM
Power connector
2-pin terminal block for DC power input. Use a Safety Extra Low Voltage (SELV) compliant limited power source (LPS) with either
a rated output power limited to ≤100 W or a rated output current limited to ≤5 A.
Function
DC ground (GND)
DC input
UL: DC power to be supplied by a UL 603 listed power supply, depending on application, with appropriate ratings.
Supervised inputs
To use supervised inputs, install end of line resistors according to the diagram below.
Parallel first connection
The resistor values must be 4.7 kΩ and 22 kΩ.
Pin
Notes
1
2
Digital input – Connect to pin 1 to activate, or leave
floating (unconnected) to deactivate.
Pin
Notes
1
2
Digital input – Connect to pin 1 to activate, or leave
floating (unconnected) to deactivate.
Pin
1
2
Notes
For powering controller when
not using Power over Ethernet.
Note: This pin can only be
used as power in.
29
Specifications
0 V DC
0 to max 30 V DC
Specifications
0 V DC
0 to max 30 V DC
Specifications
0 V DC
12 V DC, max 36 W