AXIS A1214 Network Door Controller Kit
Specifications
Auxiliary connector
Use the auxiliary connector with external devices in combination with, for example, motion detection, event triggering, and alarm
notifications. In addition to the 0 V DC reference point and power (DC output), the auxiliary connector provides the interface to:
Digital input - For connecting devices that can toggle between an open and closed circuit, for example PIR sensors, door/window
contacts, and glass break detectors.
Supervised input - Enables possibility to detect tampering on a digital input.
Digital output - For connecting external devices such as relays and LEDs. Connected devices can be activated by the VAPIX®
Application Programming Interface or from the product's webpage.
4-pin terminal block
Function
DC ground
DC output
Configurable
(Input or Output)
1
DC ground
2
DC output 12 V
3
I/O configured as input
4
I/O configured as output
External connector
Two 2-pin terminal blocks for external devices, for example glass break or fire detectors.
Pin
Notes
1
2
Can be used to power auxiliary equipment.
Note: This pin can only be used as power out.
3–4
Digital input or supervised input – Connect to pin 1 to activate, or
leave floating (unconnected) to deactivate. To use supervised input,
install end-of-line resistors. See connection diagram for information
about how to connect the resistors.
Digital output – Internally connected to pin 1 (DC ground) when
active, and floating (unconnected) when inactive. If used with an
inductive load, e.g., a relay, connect a diode in parallel with the
load, to protect against voltage transients. Each I/O is capable of
driving 12 V DC, 50 mA (max) external load, if internal 12 V DC
output (pin 2) is used. In the case of using open drain connections
in combination with an external power supply, then the I/Os can
manage DC supply of 0–30 V DC, 100 mA.
28
Specifications
0 V DC
12 V DC
Max load = 50 mA in total
0 to max 30 V DC
0 to max 30 V DC, open drain,
100 mA