Power Cables; Emergency Power Off (Epo); Shunt Trip; Epo Connection Diagram - Toshiba 1600EP Series Operation Manual

Battery cabinet system single phase – 3.6/6.0 kva
Hide thumbs Also See for 1600EP Series:
Table of Contents

Advertisement

5.3

Power Cables

The three battery cabinet connector cables (battery positive, battery negative, and
battery charger) are each equipped with individually keyed Anderson connectors to
prevent cross connecting the battery cabinet and UPS circuitry.

6.0 Emergency Power Off (EPO)

6.1

Shunt Trip

A shunt trip for the DC breaker on the battery cabinet is provided. This device is
operated with an applied voltage of 120 Vac (supplied from the UPS). When this
voltage is applied, the shunt trip will cause the breaker to switch to the OFF position
disabling the battery cabinet.
6.2

EPO Connection Diagram

The EPO is achieved by completing the circuit between 14 &15 on terminal block TB1
of the UPS. By completing the circuit, the shunt trip will cause the breaker on the
battery cabinet as well as the one on the UPS to switch to the OFF position disabling
both the battery cabinet and the UPS.
10
TOSHIBA
Terminal Block TB1 on the 1600EP UPS
1600EP Series Battery Cabinet Operation Manual