5.3

Burner start-up

Electrically power the burner using the disconnecting switch
on the boiler panel.
Close the thermostats/pressure switches and set the switch of
Fig. 27 to "1/ON".
Make sure that the lights or testers connected to
the solenoids, or the pilot lights on the solenoids
themselves, indicate that no voltage is present.
If voltage is present, stop the burner immediately
DANGER
and check the electrical connections.
As the burner is not fitted with a device to check the sequence of
the phases, it may be that the rotation of the motor is incorrect.
As soon as the burner starts up, go in front of fan motor cooling
fan and check it is rotating anticlockwise or else in the direction
of the arrow shown in the diagram Fig. 4 on page 11.
If this is not the case:
put the switch of Fig. 27 to "0/OFF" and wait until the flame
control carries out the switching off phase;
disconnect the burner form the electrical supply.
Invert the phases on the three-phase power sup-
ply. This operation must be carried out with the
electrical supply disconnected. Follow the "Start-
up procedure" on page 40.
DANGER
20205048