14 Configuration
Parameter
B2 Reset Timer
Reset ON/OFF
Reset Mode
Reset Cool SP
Reset Heat SP
INFORMATION
When the value for a parameter is "- -", this means that
when the timers expires, nothing changes for that
parameter and the current active value is kept.
Window contact B1
Contact closed (window open)
Contact open (window open)
Installer and user reference guide
24
Description
Timer that starts as soon as the
Delay Timer expires. When this
timer expires, the previous state
(i.e. regular setpoint) changes to
the "Default Reset Setting" state.
"Default Reset Setting" on/off
state
"Default Reset Setting" operation
mode
"Default Reset Setting" cooling
setpoint
"Default Reset Setting" heating
setpoint
Key card contact B2
Contact closed (key card IN)
Contact closed (key card IN)
Possible values
0-20 hours
"ON", "OFF", "--"
Auto, Cooling, Heating, Fan only,
--
See indoor unit's setpoint range
and setpoint range limitation, "--"
See indoor unit's setpoint range
and setpoint range limitation, "--"
Window contact logic
Time
—
—
Default value
"20 hours"
"OFF"
"--"
"22°C"
"22°C"
Action
▪ Normal indoor unit operation.
▪ The unit returns to the previous
state
before
opening
contact.
Unit operation is forced off:
▪ No
delay
and
reset
timer
functionality.
▪ No Setback functionality.
▪ Not possible to turn on/off the
unit with the controller's ON/OFF
button.
BRC1H519W+K+S
Wired remote controller
4P513689-1A – 2018.03
the