Address
Second level
External input interlock
About external input interlock
External input interlock allows for the integration of key card and
window contact logic into the system.
External input interlock is only available in case digital input adapter
BRP7A5* is part of the system. When the adapter is part of the
system:
▪ it is not possible to connect a second (slave) controller, and
▪ the schedule function will be disabled for as long the adapter is
connected to the indoor unit.
Make sure that the digital input adapter and its optional contacts
(window contact B1 and key card contact B2) are correctly installed.
Confirm that the voltage free contact of the digital input adapter is in
the correct position. For instructions on how to install the digital input
adapter, see the installation manual of the digital input adapter.
In case the digital input adapter does not function properly, the
external input interlock menu is not available in the installer menu.
In case a centralised controller is additionally part of the system,
external input interlock is controlled by the centralised controller. The
digital input adapter is then overruled.
To make external input interlock settings
Prerequisite: You are in the installer menu.
External input interlock settings overview
Parameter
B2 Delay Timer
BRC1H519W+K+S
Wired remote controller
4P513689-1A – 2018.03
Define an address for the indoor/outdoor unit.
To SET an address, make sure
Apply settings.
To RELEASE an address that was previously set, change
settings.
Description
Timer that starts as soon as the
key card is removed. The unit
continues normal operation until
the timer expires.
Description
is selected.
1 Navigate to the external input interlock menu.
2 Use
and
to navigate through the menu.
3 Press
to select a parameter.
4 With a parameter selected, use
parameter's value.
5 With a parameter selected, press
that parameter.
6 When you are done making settings, confirm all settings by
selecting
and pressing
Result: The system will restart and implement any changes made.
INFORMATION
For an overview of settable parameters and what they
mean, see
"External input interlock settings overview"  on
page 23.
Possible values
0-10 minutes
14 Configuration
to
and then apply
and
to change that
to confirm the value for
.
Default value
"1 min"
Installer and user reference guide
23