Vision™ OPLC™
Wiring Procedure
Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm
1. Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Input or output cables should not be run through the same multi-core cable or share the same wire.
Allow for voltage drop and noise interference with input lines used over an extended distance. Use
wire that is properly sized for the load.
I/Os
This model comprises a total of 16 digital inputs, 2 analog inputs and 16 outputs.
1. Input functionality can be adapted as follows:
All 16 inputs may be used as digital inputs. All 16 may be wired in a group, via a pin on the
connector, as either npn or pnp. In addition, according to jumper settings and appropriate wiring:
-
Inputs 160 & 162 can function as either a high-speed counter, as part of a shaft-encoder, or as
a normal digital input
-
Inputs 161 & 163 can function as either a counter reset, as part of a shaft-encoder, or as a
normal digital input
-
If inputs 160 & 162 is set as a high-speed counter (without reset), inputs 161 & 163 can function
as normal digital inputs
2. Output functionality is as follows:
-
All 15 (161-175) outputs are pnp outputs
-
Output 160 is an npn - High Speed Output
I/O Wiring (HE-10 connectors)
Unitronics
I/O Configuration
2
–3.31 mm
2
).
5