* V350-35-TU24/V350-J-TU24 comprise both RS232/485 and USB ports; note that only one channel may be used at a time. Standard Kit Contents Controller Terminal Blocks Battery (installed) Slides (2 sets of key labels) Mounting Brackets Yes (2 parts) Rubber Seal Unitronics...
All examples and diagrams are intended to aid understanding, and do not guarantee operation. Unitronics accepts no responsibility for actual use of this product based on these examples. Please dispose of this product according to local and national standards and regulations.
Page 3
DIN-rail Mounting 1. Snap the controller onto the DIN rail as shown in the figure to the right. 2. When properly mounted, the controller is squarely situated on the DIN-rail as shown in the figure to the right. Unitronics...
Page 4
- If input 0 is set as a high-speed counter (without reset), input 1 can function as a normal digital input. Inputs 7-8 and 9-10 can function as digital, thermocouple, or PT100 inputs; Input 11 can also serve as the CM signal for PT100. Unitronics...
Page 5
Input 11: Set Type - Digital or CM for PT100 Set to JP11 Digital* CM for PT100 Input 5: Set Type - Digital or Analog #3 Set to JP10 Digital* Voltage Current Input 6: Set Type - Digital or Analog #2 Set to Digital* Voltage Current *Default settings Unitronics...
Page 7
PT100 (Sensor 0): use Input 9 and 10, related to CM signal. PT100 (Sensor 1): use Input 7 and 8, related to CM signal. 4 wire PT100 can be used by leaving one of the sensor leads unconnected Unitronics...
For ground wiring uses the shortest and thickest possible wire. Communication V350-35-TU24/V350-J-TU24 models comprise built-in ports: 1 USB and 1 RS232/RS485 (Port 1). Note that physically connecting a PC to the controller via USB suspends RS232/RS485 communications via Port 1. When the PC is disconnected, RS232/RS485 resumes. Unitronics...
Page 9
Set communications to RS485, by setting both COMM jumpers to ‘485’. Set RS485 termination, by setting both TERM jumpers to ‘OFF’. To access the jumpers, you must open the controller according to the instructions on page 10. Unitronics...
Note that you must replace the back cover securely before powering up the controller. The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.