Parame-
Description
ter
Coo
First cooling setpoint
Hea
First heating setpoint
San
Sanitary setpoint
Coo2
Second cooling setpoint
Hea2
Second heating setpoint
Mixing valve summer set-
*rCO
point
*rHE
Mixing valve winter setpoint °C
H10
Sanitary function enabling
Input configuration
H17
Analogue ST6
Input configuration
H18
Analogue ST7
0-10vDC live input configu-
H22
ration
Analogue ST11
Input configuration
*H27
Analogue ST5E
Input configuration
*H28
Analogue ST6E
Input configuration
*H29
Analogue ST7E
Input configuration
H46
Digital ID2
Input configuration
H47
Digital ID3
Input configuration
H52
Digital ID8
Input configuration Digital
H53
ID9
Input configuration
*H63
Digital ID9E
H75
Digital inputs polarity
H76
Digital inputs polarity
H77
Digital inputs polarity
Output configuration
H81
In DO3 power
Output configuration
H84
In DO6 power
Output configuration
H85
In DO7 power
28
Unit
Default
Range
°C
7.0
25÷Coo2
°C
45.0
Hea2÷H01
°C
48.0
25÷H01
°C
18.0
Coo÷25
°C
35.0
25÷Hea
°C
15.0
-50÷80
30.0
-50÷80
/
0
0÷6
/
0
0÷49
/
0
0÷49
/
0
0÷49
/
0
0÷49
/
0
0÷49
/
0
0÷49
/
0
0÷30
/
2
0÷30
/
0
0÷30
/
0
0÷30
/
0
0÷30
/
0
0÷255
/
0
0÷255
/
0
0÷255
/
22
0÷47
/
6
0÷47
/
25
0÷47
Picco R32
Allowed configurations:
Visibility
Description
U
U
U
U
U
I
I
I
See par. 10.2
0 = Input disabled
I
6 = Domestic hot water probe
0 = Input disabled
I
41 = Remote water temperature
probe
0 = Input disabled
I
40 = Plant setpoint decalibration
0 = Input disabled
I
44 = Mixer probe
0 = Input disabled
I
39 = Solar storage tank probe
0 = Input disabled
I
38 = Solar collector probe
0 = Input disabled
I
3 = Summer/winter mode change
0 = Input disabled
I
2 = Remote On / Off
0 = Input disabled
I
28 = DHW thermostat call
0 = Input disabled
21= Hz min/max remote
I
25= Silenced version
26 = Double set-point call
0 = Input disabled
I
19 = room thermostat
0 = Digital inputs N.A.
1 = ID1 polarity inverted
2 = ID2 polarity inverted
4 = ID3 polarity inverted
I
8 = ID4 polarity inverted
16 = ID5 polarity inverted
32 = ID6 polarity inverted
64 = ID7 polarity inverted
128 = ID8 polarity inverted
0 = Digital inputs N.A.
1 = ID9 polarity inverted
2 = ID10 polarity inverted
4 = ID1E1 polarity inverted
I
8 = ID2E1 polarity inverted
16 = ID3E1 polarity inverted
32 = ID4E1 polarity inverted
64 = ID5E1 polarity inverted
128 = ID6E1 polarity inverted
0 = Digital inputs N.A.
1 = ID7E1 polarity inverted
2 = ID8E1 polarity inverted
4 = ID9E1 polarity inverted
I
8 = ID10E1 polarity inverted
16 = ID1E2 polarity inverted
32 = ID2E2 polarity inverted
64 = ID3E2 polarity inverted
128 = ID4E2 polarity inverted
0 = Output disabled
I
22 = Plant integration heater
26 = DHW integration heater
0 = Output disabled
I
6 = DHW valve
0 = Output disabled
25 = Double set-point valve
29 = Boiler enabling
24 = Alarm warning
l
31 = Summer/winter operating
mode warning
21 = Defrost warning
47 = Machine block warning
Heat pumps inverter air/water with axial fans
Notes
If sanitary function
active. See par. 10.2
Config if Gi accessory
present
Config if Gi accessory
present
Only if Gi accessory
present
Only if Gi accessory
present
Only if Gi accessory
present
Only if Gi accessory
present