Example of single phase unit terminal block
X12-2
X12-2
6. EDITING DYNAMIC SET-POINT
The regulator allows you to modify the set-point by adding up the value according to the temperature of the outdoor air probe. To use this func-
tion, edit the values from parameter b08 to b14 following the information below (edited by the installer).
Parameters of regulator PAr -> rE
• b08 enable = 1/disable=0 dynamic set-point.
• b09 = maximum cooling offset.
• b10 = maximum heating offset.
• b11 = Cooling outdoor temperature setting.
• b12 = Heating outdoor temperature setting.
• b13 = Cooling temperature delta.
• b14 = Heating temperature delta.
Edit the setpoint depending on the outdoor temperature:
Temp.
set
Offset >0
b10
Hea
b14
Delta <0
6.1 SETTINGS FOR STANDARD CLIMATIC CURVES
60
E
55
D
50
C
45
40
B
35
A
30
25
20
15
-15
-10
-5
Setpoint
CURVE
Heat
A
20°C
B
20°C
X-22.1
X-20.1
X-19.1
X-17.1
X-15.1
X12-1
X-22.2
X-20.2
X-19.2
X-17.2
X-15.2
X12-1
X-22.2
X-20.2
X-19.2
X-17.2
X-15.2
X-22.1
X-20.1
X-19.1
X-17.1
X-15.1
HEATING
Set temp. ext
b12
Delta >0
HEATING
Fan Coil
Under floor
0
5
10
15
20
Setpoint
b08
Cool
--
1
--
1
Picco R32
X-16.1
X-5.1
X-14.1
X-11.1
X-10.1
X-16.2
X-5.2
X-4.1
X-14.2
X-11.2
X-10.2
X-16.2
X-5.2
X-4.1
X-14.2
X-11.2
X-10.2
X-16.1
X-5.1
X-14.1
X-11.1
X-10.1
SETPOINT DINAMICO - RAFFRESCAMENTO
Temp.
set
Coo
Offset <0
Temp.
ext
20
G
15
F
10
5
0
15
25
B09
b10
--
13°C
--
18°C
Heat pumps inverter air/water with axial fans
N
L
X-1.1
X-9.1
X-6.1
X-9.2
X-6.2
F1
X-9.2
X-6.2
N
L
X-1.1
X-9.1
X-6.1
COOLING
Set temp. ext
b11
b13
Delta <0
Delta >0
COOLING
20
25
30
35
B11
b12
B13
--
20°C
--
20°C
b09
Temp.
ext
40
45
b14
--
-25°C
--
-27°C
13