Final Checks (With Burner Operating) - Riello DB 12 LM C10 Installation, Use And Maintenance Instructions

Light oil burner
Table of Contents

Advertisement

Available languages

Available languages

5.9

Final checks (with burner operating)

 Open the thermostat/pressure switch TL
 Open the thermostat/pressure switch TS
 Turn the air pressure switch to the maximum end of scale
position
 Turn off the burner and cut off the power
 Disconnect the wire of the flame sensor
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
WARNING
20198588
Start-up, calibration and operation of the burner
The burner must stop
The burner must stop in lockout
The burner must not start
The burner must stop in lockout due to ignition failure
26
GB
Tab. J

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

20198536

Table of Contents