5.4
Air / fuel adjustment
During the operations for calibrating the air/fuel ratio for oil burn-
ers, the following adjustments need to be made.
5.4.1
Oil pump outlet pressure
Turn the screw 1)(Fig. 24) on the pump.
5.4.2
Air cam
Use the adjusters 2)(Fig. 25) after loosening the screws 3).
Key (Fig. 25)
1
Cam
2
Adjustment screws
3
Locking screws
4
Adjustable profile
5.4.3
Oil cam
Modify the eccentricity by turning the screw 3)(Fig. 26) after hav-
ing loosened the screws 2).
By tightening the screw 3) the eccentricity increases, thereby in-
creasing the difference between the maximum and minimum re-
turn pressure of the nozzle.
Key (Fig. 26)
1
Eccentric screw
2
Screws
3
Eccentricity adjustment screw
4
Nut and lock nut
5
Stop ring
6
Delivery pressure gauge
7
Return pressure gauge