MAINTENANCE PROGRAM
REMOVING
THE BLAST TUBE
POSITION OF ELECTRODES
ATTENTION:
Check the position of the electrodes after any intervention as wrong position could cause ignition troubles.
Elettrodo di rivelazione
Ionization Probe
20 mm
SECTION B-B
GAS FILTER CLEANING
22
www.ecoflam-burners.com
B
59 mm
A
B
min. 6
μA
Siemens LFL1.622
Siemens LFL1.333
Microammeter
50 μA end of scale
SECTION A-A
A
The ionization current is checked by inserting a microammeter with
an end scale of 50 μA (d.c.) in series with the ionization probe.
A faulty position of the electrode can lead to a reduction in the
24
ionization current and cause a safety shut off of the burner due to
a flame detection failure. In this case, check the position of the
electrode, its electric connection and the earthing of the burner.
The ionization current is normally > 20 μA.
REMOVING
THE FIRING HEAD
Ignition Electrode
Elettrodo di accensione