INSTALLATION
Gas pressure loss diagrams
!
PRESSURE DROP includes: "COMBUSTION HEAD + GAS TRAIN + GAS GOVERNOR & FILTER" as per EN676 Standard.
Back pressure of boiler (or other applications) must be added/included in order to have the total min pressure drop.
Burner
BLU 5000.1 PR
MULTICALOR 500.1
MULTIFLAM 500.1
LEGENDA
Pf: Back pressure of furnace
Pb: Pressure of burner (combustion head + complete gas train)
Pin: Minimum inlet pressure
14
www.ecoflam-burners.com
Advisable gas
Gas train
governor & filter
no
VGD 40.125
FILTER DN 125
no
VGD 40.100
FILTER DN 100
no
VGD 40.080
FILTER DN 80
no
VGD 40.065
FILTER DN 65
no
VGD 20.503
FILTER 2"
300
290
natural gas
280
270
260
250
240
230
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
200
250
Inlet gas pressure
Spring color
yellow
yellow
yellow
yellow
yellow
300
350
400
450
500
flow m
3
/h
Inlet gas pressure
MIN [mbar]
MAX [mbar]
33
500
35
500
40
500
45
500
60
500
75
500
110
500
140
500
210
500
250
500
VGD 20.503 + F- 2"
VGD 20.503
VGD 40.065 + F- DN 65
VGD 40.065
VGD 40.080 + F- DN 80
VGD 40.080
VGD 40.100 + F- DN100
VGD 40.100
VGD 40.125 + F- DN125
VGD 40.125
550
600
3C
420010480101