Connecting a 3-kW Universal AC/DC Power Supply to an AC Power Source

Connecting a 3-kW Universal AC/DC Power Supply to an AC Power Source
The 3-kW Universal AC/DC power supply can be connected to either a 200-to-277-V AC circuit equipped
with a Saf-D-Grid receptacle. This procedure is for connecting the power supply to an AC power source.
Before you begin
The power switch on the power supply must be turned off (power switch set to 0).
Step 1
Verify that the power switch on the power supply is turned off (0).
Step 2
Connect the Saf-D-Grid connector on the AC power cable to the Saf-D-Grid receptacle for the AC power source.
Step 3
Connect the Saf-D-Grid connector on the other end of the power cable to the Saf-D-Grid receptacle on the power supply.
Step 4
Turn on the power supply by pressing its power switch to on (1).
Step 5
Verify that the Output Power LED turns on and becomes green.
What to do next
After you finish connecting the power supplies to the power source and the power supplies are operating, you
connect the switch to the network.

Connecting a 3-kW Universal AC/DC Power Supply to a DC Power Source

The 3-kW Universal AC/DC power supply can be connected to a 240-to-380-V DC circuit equipped with
positive, negative, and ground terminals. This procedure is for connecting the power supply to a DC power
source.
Before you begin
• The DC power source must be turned off at its circuit breaker.
• The power switch on the power supply must be turned off (power switch set to 0).
Step 1
Verify that the circuit breaker for the DC power source is turned off.
Step 2
Verify that the power switch on the power supply is turned off (0).
Step 3
Connect the ground terminal ring on the power cable to the ground terminal on the DC power source. Secure it in place
with a nut tightened to the appropriate torque setting for the terminal post.
Step 4
Connect the negative terminal ring on the power cable to the negative (-) terminal on the DC power source. Secure it in
place with a nut tightened to the appropriate torque setting for the terminal post.
Step 5
Connect the positive terminal ring on the power cable to the negative (+) terminal on the DC power source. Secure it in
place with a nut tightened to the appropriate torque setting for the terminal post.
Step 6
Connect the Saf-D-Grid connector on the other end of the power cable to the Saf-D-Grid receptacle on the power supply.
Step 7
Turn on the circuit breaker for the DC power source circuit.
Step 8
Turn on the power supply by pressing its power switch to on (1).