Installing A Chassis; Installing A Rack Or Cabinet - Cisco Nexus 9508 Hardware Installation Manual

Aci-mode switch
Hide thumbs Also See for Nexus 9508:
Table of Contents

Advertisement

Installing a Chassis

Installing a Rack or Cabinet

Before you install the switch, you must install a standard four-post, 19-inch (48.3-cm) EIA data center rack
(or a cabinet that contains such a rack) that meets the requirements that are listed in
Requirements, on page
Warning
Warning
Bolt the rack to the subfloor before moving the chassis onto it.
Step 2
If the rack has bonded construction, connect it to the earth ground. This action enables you to ground the switch and its
components and to ground your electrostatic discharge (ESD) wrist strap. This action prevents discharge damage when
you handle ungrounded components during installation.
Step 3
If you need access to the source power at the rack, include one of the following:
14.
Statement 1048 Rack Stabilization
The rack stabilizing mechanism must be in place, or the rack must be bolted to the floor before installation
or servicing. Failure to stabilize the rack can cause bodily injury.
Statement 1018 Supply Circuit
To reduce risk of electric shock and fire, take care when connecting units to the supply circuit so that
wiring is not overloaded.
C H A P T E R
Cisco Nexus 9508 ACI-Mode Switch Hardware Installation Guide
3
Rack and Cabinet
19

Advertisement

Table of Contents
loading

Table of Contents