Example Of Reportdatacmd - netvox R718N3 E Series User Manual

Wireless 3-phase current meter
Table of Contents

Advertisement

5.1 Example of ReportDataCmd

FPort:0x06
Bytes
1
Version
Version– 1 byte –0x01——the Version of NetvoxLoRaWAN Application Command Version
DeviceType– 1 byte – Device Type of Device
ReportType – 1 byte –the presentation of the NetvoxPayLoadData, according the devicetype
NetvoxPayLoadData– Fixed bytes (Fixed =8bytes)
Tips
1. Battery Voltage:
The voltage value is bit 0 ~ bit 6, bit 7=0 is normal voltage, and bit 7=1 is low voltage.
Battery=0xA0, binary=1010 0000, if bit 7= 1, it means low voltage.
The actual voltage is 0010 0000 = 0x20 = 32, 32*0.1v =3.2v
2. Version Packet:
When Report Type=0x00 is the version packet, such as 014A000A02202207080000, the firmware version is 2022.07.08.
3. Data Packet:
When Report Type=0x01 is data packet; If the device data exceeds 11 bytes or there are shared data packets, the Report Type will
have different values.
Device
Report
Device
Type
Type
0x00
0x01
R718N3xxx(E)
0x4A
Series
0x02
0x03
1
1
DeviceType
ReportType
SoftwareVersion
HardwareVersion
(1Byte)
(1Byte)
Eg.0x0A—V1.0
Battery
Current1
(1Byte,
(2Bytes,
unit:0.1V)
unit:1mA)
Mulitplier2
Battery
(1Byte),
(1Byte,
the real current2
unit:0.1V)
should convert with
Current* Mulitplier
Battery
Current1
(1Byte,
(2Bytes,
NetvoxPayLoadData
NetvoxPayLoadData
DateCode
(4Bytes,
eg 0x20170503)
Current2
Current3
(2Bytes,
(2Bytes,
unit:1mA)
unit:1mA)
Mulitplier3
(1Byte),
the real current3
should convert with
Current* Mulitplier
Current2
Current3
(2Bytes,
(2Bytes,
6
Var (Fix=8 Bytes)
Reserved
(2Bytes,fixed 0x00)
Mulitplier1(1Byte),
the real current1 should convert with
Current* Mulitplier
Reserved
(5Bytes,fixed 0x00)
Multiplier (1Byte),
BIT0-1:

Advertisement

Table of Contents
loading

Table of Contents