Electrodes Adjustment - Unigas HTLX 1025.1 Installation Manual

Table of Contents

Advertisement

Cleaning/replacing the electrodes
ATTENTION: avoid the electrodes to get in touch with metallic parts (blast tube, head, etc.), otherwise the boiler
operation would be compromised. Check the electrodes position after any intervention on the combustion head.
To remove the oil gun, proceed as follows:
1
remove the combustion head as described on the prevoius paragraph;
2
loosen the VL screw and remove the oil gun and the electrodes: check the oil gun, replace it if necessary;
3
after removing the oil gun, unscrew the nozzle and replace it if necessary;
4
in order to replace the electrodes, unscrew the VE fixing screws and remove them: place the new electrodes being careful to
observe the measures showed on pag.: reassemlbe following the reversed procedure.
Caution: adjust the nozzle position according to the air pipe, by means of the VU screw, ance the VL screw is fastened.

Electrodes Adjustment

Important Note: Check the ignition and detection electrodes after removing/adjusting the combustion head.Adjust the electrodes posi-
tion, according to the quotes shown othe next picture
37
ATTENTION: avoid the ignition and detection electrodes to contact metallic parts (blast tube, head, etc.), other-
wise the boiler's operation would be compromised. Check the electrodes position after any intervention on the
combustion head.
Checking the detection current
To check the detection signal follow the scheme in the picture below. If the signal is less than the value indicated, check the position of
the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.
Minimum detection signal: 3.5Vdc
VU
A
D
Fig. 14 - Detection with detector QRI...
43
VE
VL
C
A:
 mm
B:
8 mm
C:
 mm
D:
5 mm
PART III: MAINTENANCE

Advertisement

Table of Contents
loading

This manual is also suitable for:

Htlx 1030rHtlx 1030.1

Table of Contents