Unigas HTLX 1025.1 Installation Manual page 17

Table of Contents

Advertisement

Installation diagram of light oil pipes
PLEASE READ CAREFULLY THE "WARNINGS" CHAPTER AT THE BEGINNING OF THIS MANUAL.
The burner is supplied with filter and flexible hoses, all the parts upstream the filter and downstream the return flexible hose, must be
installed by the customer. As far as the hoses connection, see the related paragraph.
Key
1
Burner
2
Flexible hoses (fitted)
3
Light oil filter (fitted)
4
Automatic interceptor (*)
5
One-way valve (*)
6
Gate valve
7
Quick-closing gate-valve (outside the tank or boiler rooms)
The pumps that are used can be installed both into single-pipe and double-pipe systems.
Single-pipe system: a single pipe drives the oil from the tank to the pump's inlet. Then, from the pump, the pressurised oil is driven to
the nozzle: a part comes out from the nozzle while the othe part goes back to the pump. In this system, the by-pass pulg, if provided,
must be removed and the optional return port, on the pump's body, must be sealed by steel plug and washer.
Double-pipe system: as for the single pipe system, a pipe that connects the tank to the pump's inlet is used besides another pipe that
connects the pum's return port to the tank, as well. The excess of oil goes back to the tank: this installation can be considered self-ble-
eding. If provided, the inside by-pass plug must be installed to avoid air and fuel passing through the pump.
Burners come out from the factory provided for double-stage systems. They can be suited for single-pipe system (recommended in the
case of gravity feed) as decribed before.To change from a 1-pipe system to a 2-pipe-system, insert the by-pass plug G (as for ccw-rota-
tion- referring to the pump shaft).
Caution: Changing the direction of rotation, all connections on top and side are reversed.
pipeline length in meters.
G
Bleed
Bleeding in two-pipe operation is automatic : it is assured by a bleed flat on the piston. In one-pipe operation, the plug of a pressure
gauge port must be loosened until the air is evacuated from the system.
From tank
To tank
Double-pipe system
Рис. 1
Suntec TA
(*) Only for installations with gravity, siphon or forced
circulation feed systems. If the device installed is a
solenoid valve, a timer must be installed to delay the
valve closing.
The direct connection of the device without a timer
may cause pump breaks.
Suntec T
17
PART I: INSTALLATION MANUAL
G

Advertisement

Table of Contents
loading

This manual is also suitable for:

Htlx 1030rHtlx 1030.1

Table of Contents