Unigas TLX2020 Installation Manual page 27

Table of Contents

Advertisement

Choose "LoadController" and press ENTER: the following menu is shown:
Choose "ControllerParam" and press ENTER: the following menu is shown:
Choose "SetPointW1" and press ENTER:
Curr: it shows the current set-point; use the arrows keys to change.
NOTE: the availabel range for this parameter depends on the probe provided; the unit measure of the detected value and its limits are
bound up with parameters set at the "Service" level.
Once the new set-point is set, confirm by pressing ENTER, otherwise exit without changings by pressing ESC.
Press ESC to exit the set-point programming mode.
Once the temperature set-point W1 is imposed, set the Switch-on (SDon) and the Switch-off (SDoff) point of the 2-position controller:
SDoff
W
SDon
To set these values, select the item SD_ModOn (SDOn), by scrolling down the "Load controller" menu with the arrow keys and press
ENTER:
the display will show:
The deafult value for this parameter is1% that is, the burner will light again at a temperature 1% lower than the set-point. Change value,
BurnerControl
RatioControl
O2Contr./Guard.
LoadController
ControllerParam
Configuration
Adaption
SW Version
ContrlParamList
MinActuatorStep
SW_FilterTmeCon
SetPointW1
SetpointW1
Curr:
New:
Setpoint
Actual value
SetpointW1
SetpointW2
SD_ModOn
SD_ModOff
SD_ModOn
Curr::
New:
27
90°
90°
1.0%
1.0%
PART III: OPERATION