Unigas TLX83 Manual Of Installation - Use - Maintenance

Gas burners
Table of Contents

Advertisement

Quick Links

TLX83
LMV5x
Microprocessor controlled
Gas burners
MANUAL OF INSTALLATION - USE - MAINTENANCE
BURNERS - BRUCIATORI - BRULERS - BRENNER - QUEMADORES - ГОРЕЛКИ
M039598CA 0.0 09/2020

Advertisement

Table of Contents
loading

Summary of Contents for Unigas TLX83

  • Page 1 TLX83 LMV5x Microprocessor controlled Gas burners MANUAL OF INSTALLATION - USE - MAINTENANCE BURNERS - BRUCIATORI - BRULERS - BRENNER - QUEMADORES - ГОРЕЛКИ M039598CA 0.0 09/2020...
  • Page 2 DANGERS, WARNINGS AND NOTES OF CAUTION THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE USER. INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOWING PRODUCT INSTALLATION AND MAINTENANCE.
  • Page 3 3b) FIRING WITH GAS, LIGHT OIL OR OTHER FUELS DIRECTIVES AND STANDARDS Gas burners GENERAL European directives  The burner shall be installed by qualified personnel and in compliance -Regulation 2016/426/UE (appliances burning gaseous fuels) with regulations and provisions in force; wrong installation can cause -2014/35/UE (Low Tension Directive) injuries to people and animals, or damage to property, for which the -2014/30/UE (Electromagnetic compatibility Directive)
  • Page 4 Burner data plate Type Gas - Light oil burners For the following information, please refer to Model Year European Directives the data plate: S.Number -Regulation 2016/426/UE (appliances burning gaseous fuels) burner type and burner model: must be Output  Oil Flow -2014/35/UE (Low Tension Directive) reported in any communication with the Fuel...
  • Page 5 PART I: SPECIFICATIONS PART I: SPECIFICATIONS BURNERS FEATURES Burner model identification Burners are identified by burner type and model. Burner model identification is described as follows. Type TLX83 Model MD. L. BURNER TYPE TLX83 FUEL M - Natural gas OPERATION (Available versions)
  • Page 6 PART I: SPECIFICATIONS Technical Specifications BURNER TYPE TLX83 M-.. Output min. - max. kW 200 - 830 Fuel Natural gas Category see next paragraph Gas flow rate 21 - 88 min.-max. Stm Gas pressure min.-max. mbar (see Note 2) Electric supply...
  • Page 7 Overall dimensions (mm) N°14 AIR INLET FLANGEI Ø BURNER FLANGE BOILER RECOMMENDED DRILLING TEMPLATE...
  • Page 8 Pressure in the Network / gas flow rate curves Natural Gas burners  TLX83 Gas rate Stm ATTENTION: the gas rate value is quoted on the x-axis, the related network pressure is quoted on the y-axis (pressure value in the combustion chamber is not included). To know the minimum pressure at the gas train inlet, necessary to get the requested gas rate, add the pressure value in the combustion chamber to the value read on the y-axis.
  • Page 9 PART I: SPECIFICATIONS WARNING: the diagrams refers to natural gas. For different type of fuel please refer to the paragraph “Fuel” at the beginning of this chapter. Combustion head gas pressure curves Combustion head gas pressure depends on gas flow and combustion chamber backpressure. When backpressure is subtracted, i depends only on gas flow, provided combustion is properly adjusted, flue gases residual O2 percentage complies with “Recommended combustion values”...
  • Page 10 PART I: SPECIFICATIONS Connection diagram of the air pressure switch to the burner air conduct Burner air pressure switch Iron sleeve Ø 10 mm Male elbow fitting Ø 6 mm x 10 Copper tube Ø 6 mm x 1,5 mt Air conduct Nut for male elbow fitting Ø...
  • Page 11 PART II: INSTALLATION PART II: INSTALLATION MOUNTING AND CONNECTING THE BURNER Packing The burners are despatched in wooden crates whose dimensions are: 1490mm x 840mm x 700mm (L x P x H).  Packing cases of this type are affected by humidity and are not suitable for stacking. The following are placed in each packing case: burner with gas train;...
  • Page 12 PART II: INSTALLATION Fitting the burner to the boiler To install the burner into the boiler, proceed as follows: make a hole on the closing door of the combustion chamber as described on paragraph “Overall dimensions”) place the burner to the boiler: lift it up and handle it according to the procedure described on paragraph “Handling the burner”; place the 4 stud bolts (5), according to the burner’s drilling plate described on paragraph “Overall dimensions”;...
  • Page 13 PART II: INSTALLATION GAS TRAIN CONNECTIONS The diagrams show the components of the gas train included in the delivery and which must be fitted by the installer.The diagrams are in compliance with the current laws. Procedure to install the double gas valve unit: two (2) gas flanges are required;...
  • Page 14 PART II: INSTALLATION MultiBloc MB-DLE - Assembling the gas train ”direction” arrows for gas supply network installation Keys Gasket Gas filter Gas valves group Bellows unit Manual valve MULTIBLOC DUNGS Mounting Mount flange onto tube lines: use appropriate sealing agent MB-DLE 405..412 Insert MB-DLE: note position of O rings MB-DLE 415..420...
  • Page 15 PART II: INSTALLATION ELECTRICAL CONNECTIONS WARNING! Respect the basic safety rules. make sure of the connection to the earthing system. do not reverse the phase and neutral connections. fit a differential thermal magnet switch adequate for connection to the mains. WARNING! before executing the electrical connections, pay attention to turn the plant’s switch to OFF and be sure that the burner’s main switch is in 0 position (OFF) too.
  • Page 16 PART III: OPERATION PART III: OPERATION LIMITATIONS OF USE THE BURNER IS AN APPLIANCE DESIGNED AND CONSTRUCTED TO OPERATE ONLY AFTER BEING CORRECTLY CONNEC- TED TO A HEAT GENERATOR (E.G. BOILER, HOT AIR GENERATOR, FURNACE, ETC.), ANY OTHER USE IS TO BE CONSIDE- RED IMPROPER AND THEREFORE DANGEROUS.
  • Page 17 PART III: OPERATION ADJUSTING AIR AND GAS FLOW RATES Adjusting air and gas flow rates WARNING! During commissioning operations, do not let the burner operate with insufficient air flow (danger of formation of carbon monoxide); if this should happen, make the fuel decrease slowly until the normal combustion values are achieved.
  • Page 18 PART III: OPERATION Siemens VGD.. Now adjust the pressure switches (see next par.). Start-up procedure Turn the burner on. the LMV control box starts the system test cycle: the AZL display shows the System Test message; at the end of the test, it shows the main page and the system stops (the safety chain is open) waiting for the startup enabling signal (standby - Program phase no.
  • Page 19 PART III: OPERATION Second page Fuel: it shows (in degrees) the fuel actuator position. Air: it shows (in degrees) the air actuator position. Ax1..3: auxiliaries. VSD: % value on the inverter maximum frequency O2: oxygen percentage Ld: load percentage (burner output). Press the ENTER key to go back to the main page.
  • Page 20 PART III: OPERATION 10.08.07 13.47 C:71 D:00 Start No. Load alternating by an error message as: No flame at end of safety time To see the other Lockout History pages, press the arrow keys. To exit the Lockout History pages, press ESC. Setting the temperature/pressure set-point value To set the temperature/pressure set-point value, that is the generator operating temperature/pressure;...
  • Page 21 PART III: OPERATION Choose “SetPointW1” and press ENTER: SetpointW1 Curr: 90° New: 90° Curr: it shows the current set-point; use the arrows keys to change. NOTE: the availabel range for this parameter depends on the probe provided; the unit measure of the detected value and its limits are bound up with parameters set at the “Service”...
  • Page 22 PART III: OPERATION BurnerControl RatioControl O2Contr./Guard. LoadController scroll this menu down until the tiem “AZL” is reached LoadController Actuators VSD Module confirm by pressing ENTER: Times Languages DateFormat PhysicalUnits Times: it sets the “Summer (SUM) Time / Winter (WIN) Time” operation and the continent (EU - Europe; US - United States) Sum/Winter Time Time EU/US choose the Summertime/Wintertime mode desired and cofirm by pressing ENTER;...
  • Page 23 PART III: OPERATION Settable temperature units: °C or °F Settable pressure units: bar or psi. choose the desired unit and cofirm by pressing ENTER; press ESC to exit.  choose the temperature and pressure unit and cofirm by pressing ENTER; press ESC to exit. ...
  • Page 24 PART III: OPERATION Autom/Manual/Off Curr:: Automatic New: Burner On three modes are provided: Automatic: automatic operation Burner on: manual operation Burner off: burner in stand-by If the BurnerOn mode is choosen,the burner does not follow the modulator and probe settings, but operates at the set load. Caution: if BurnerOff mode is selected, the burner stays in stand-by.
  • Page 25 PART III: OPERATION Calibration air and gas pressure switches The air pressure switch locks the control box if the air pressure is not the one requested. If it happens, unlock the burner by means of the control box unlock pushbutton, placed on the bur- ner control panel.
  • Page 26 PART IV: MAINTENANCE PART IV: MAINTENANCE At least once a year carry out the maintenance operations listed below. In the case of seasonal servicing, it is recommended to carry out the maintenance at the end of each heating season; in the case of continuous operation the maintenance is carried out every 6 months.
  • Page 27 PART IV: MAINTENANCE Output flange 1 Electrical connection for valves 10 Test point connection M4 downstream of valve 2 2 Operation display (optional) 11 Gas flow direction 3 Pressure governor closing tap 12 Test connection G 1/8 downstream of valve 1, on both sides 4 Start setting cap 13 Vent nozzle pressure regulator 5 Hydraulic brake and rate regulator...
  • Page 28 PART IV: MAINTENANCE To replace the electrodes, proceed as follows: Detection remove the burner cover electrode disconnect the electrodes cables; loose the screws of the electrodes (VB); remove the ignition electrodes and replace them paying atten- tion to the measures shown in figure. Ignition electrode Adjust the electrodes position, according to the quotes shown othe next picture.
  • Page 29 PART IV: MAINTENANCE TROUBLESHOOTNG GUIDE Gas operation * No electric power supply * Restore power supply * Main switch open * Close switch * Thermostats open * Check set points and thermostat connections * Bad thermostat set point or broken thermostat * Reset or replace the thermostat * No gas pressure * Restore gas pressure...
  • Page 30 PART IV: MAINTENANCE...
  • Page 32 C.I.B. UNIGAS S.p.A. Via L.Galvani, 9 - 35011 Campodarsego (PD) - ITALY Tel. +39 049 9200944 - Fax +39 049 9200945/9201269 web site: www.cibunigas.it - e-mail: cibunigas@cibunigas.it Note: specifications and data subject to change. Errors and omissions excepted.
  • Page 33 Siemens LMV5x Service Manual M12920CC rev 2.1 08/2017...
  • Page 34 Warnings: To avoid injury to persons, damage to property or the environment, the following warning notes must be observed Qualified personal In the sense of this documentation, qualified personal are those who are knowledgeable and qualified to install, mount, commission, operate and service / maintain LMV5 system together with burner &...
  • Page 35: Table Of Contents

        WIRING RECOMMENDATIONS ....................................... 4     Earthing ......................................4     1.1.1 TN earthing system ................................4     1.1.2 Protective Earth (PE) and Functional Earth (FE) ........................4     .Frequency inverter / Variable Speed Drive (VSD) ......................... 5  ...
  • Page 36: Wiring Recommendations

    1 WIRING RECOMMENDATIONS Earthing 1.1.1 TN earthing system For the LMV5x-System it is preconditioned that a TN earthing system is used. In a TN earthing system, one of the points in the generator or transformer is connected with earth, usually the star point in a three-phase system. TN−S: PE and N are separate conductors that are connected together only near the power source.
  • Page 37: Frequency Inverter / Variable Speed Drive (Vsd)

    .Frequency inverter / Variable Speed Drive (VSD) A VSD is one of the strongest EMC sources in a boiler house, so the following is recommended: LMV5 hi ld Earth Note: If the LMV5 is mounted in a cabinet, alternative to (X73.6 / FE), also a connection with the PE- rail in the cabinet is possible Use only VSD with EMC- filter!
  • Page 38: Recommendations

    1.3.1 Recommendations It is recommended to use a metal "mounting plate" for the LMV5 Base Unit and the Transformer AGG5.220. Use this plate to provide the Functional Earth (FE), see also /EARTH connection example The connection of the FE to the LMV5 has to be made by connecting the X52.4 terminal with FE! Follow exactly the shield and earth connection in the wiring diagram In some cases connecting the terminal X52.2 with FE results in an improved EMC- immunity of the LMV5.
  • Page 39: Wireway And Electrical Conduit

    Wireway and electrical conduit The following cables are recommended for separate wiring; Complete separate from all other cables: • Cable for "VSD to Fan motor" Line voltage, see also "1. Frequency inverter / Variable Speed Drive (VSD)" • Cable for ignition high voltage, see also "2. Ignition" •...
  • Page 41: Servomotor Wiring Example

    1.4.1 Servomotor wiring example 1.4.2 Bus cable wiring on LMV5x and AZL doors. 1.4.3 EARTH connection example...
  • Page 42: Azl Display/Programming Unit

    2 AZL display/programming unit Users can set only the LMV parameters that can be accessed without password: (see “Adjusting the temperature set-point”). The Siemens AZL User Interface allows programming the Siemens LMV control box and monitoring the system data. The user interface is made of: display: it shows menus and parameters key (previous level): it goes back to the previous level menu or exits the programming mode without changing...
  • Page 43: Lmv5X Program Operating Phases

    LMV5x program operating phases Phase number Description Sequence Home run Stand by 20,21 Waiting to start realase Startup Start fan on Startup Driving to pre-purge Startup 30..34 Pre purging Startup Driving to ignition pos Startup Ingnition pos Startup 40,42,44 Fuel release 1 Startup 50,52 Fuel release 2...
  • Page 44: Lmv5X Program Structure

    LMV5x program structure...
  • Page 45: Burner Id Number

    NOTE: (1) only for LMV52.400, LMV51.300 without temperature compensation (2) only for LMV5.200 (controlling the oxygen level in the exhaust gas flue) and LMV52.400 (monitoring the oxygen level in the exhaust gas flue, a lock out occur if a limit value is overcoming) (3) Only for LMV51.300 (in this case VSD cannot be used), LMV52.xxx ATTENTION: LMV51.300: HAS ONE AUX.
  • Page 46: Password

    Password 2.4.1 Access to service levels by password Depending on password (service or OEM), different parameters are visible. "Service" parameters, as per the actuator curves and the set-point values, are password protected. The operator must logon using the "9876" password. "User"...
  • Page 47: Thermostatic Series And Safety Loop

    3 Thermostatic series and safety loop The burner shuts down properly when the thermostatic series (X5-03.1 and X5-03.4 - terminals 3 and 4 of the burner terminal block) opens. In this way, before shut-down, the burner drives to the minimum load, then the fuel valve will close. The post-purging phase will be performed if set. By re-closing the thermostatic series, the burner will start-up again.
  • Page 48: Actuators

    4 Actuators Addressing the actuators The addressing assigns to each actuator its proper function. The addressing is factory set by the burner manufacturer. If an actuator must be replaced, it is necessary to address it, otherwise the system will not work. The parameter that sets the actuator function is protected by the Service level password.
  • Page 49: Actuator Doors Configuration

    Actuator doors configuration After the adressing of the actuators, it is necessary to activate and to configure the operation way for each servomotor. ATTENTION: Activate only the actuators that are really present, otherwise an error will occur. 1st level 2nd level 3rd level 4th level Possible choices...
  • Page 50: Setting The Load Controller

    5 Setting the load controller Door X60 is used for IntLC... choice and a temperature modulationg probe is used. ATTENTION: in case of FGR, it is not possible to connect a modulating temperature probe at the X60 door of the LMX5...
  • Page 51: Setting The Probes And Set-Points

    ExtLC X5-03 = three-point external controller (X5-03 terminals) Int LC = internal controller (LMV5x) (it switches between 2 set points, W1,W2 set thought AZL. the switch from W1 and W2 is realized opening/closing the LMV5x... terminals X62.1, X62.2). Int LC Bus = internal controller and set point setting via bus connection Int LC X62 = internal controller (LMV), but set point is externally controlled by means of a voltage/current signal on X62 terminals Ext LC X62 = external controller, the burner output is controlled by means of a voltage/current signal on X62 terminals Ext LC Bus = external controller, the burner output is controlled via bus...
  • Page 52: Configuration Of A Pressure Or A Temperature Probe Type At X61 Door

    Configuration of a pressure or a temperature probe type at X61 door ATTENTION: If the external load controller is set do not connected to terminals X60 or X61. If a modulation probe is connected to the X61 terminal, proceeding as follows: 1st level 2nd level 3rd level...
  • Page 53: Setting The Setpoint And The Burner And The Pid Operative Band

    Setting the setpoint and the burner and the PID operative band. 6.4.1 Set-point To set the temperature set-point value, that is the generator operating temperature; proceed as follows. 1st level 2nd level 3rd level 4th level 5th level 6th level Description Params &...
  • Page 54: Pid Control Parameters

    The default value for this parameter is10% that is, the burner will turn off at a temperature 1% higher than the set-point. Press the ENTER to confirm, the press ESC to exit. Otherwise press ESC to exit without changing data. Press the ESC to exit 6.4.3 PID control parameters The controller’s memory contains 5 standard parameter sets.
  • Page 55: Setting Functions "Tl_Threshoff" And "Tl_Sd_On

    Setting functions “TL_ThreshOff” and “TL_SD_On” These functions enable the settable threshold for the immediate shutdown, if value set on TL_ThreshOff is exceeded. The automatic restart is performed for values lower than the one set on TL_SD_On. On display, values detected by temperature/pressure probe are shown at the same time. TL_ThreshOff turns the burner off if temperature exceeds the set value.
  • Page 56: Vsd Standardization

    7 VSD Standardization Motor standardization (speed acquisition) allows the LMV unit to control the motor rounds at the maximum frequency signal coming from the VSD. A temporary standardization is factory set only for test purpose. The definite standardization must be performed on site by the Service Center (only if the fan is supplied), before the plant test.
  • Page 57: Special Positions

    8 SPECIAL POSITIONS Ignition position The ignition point is independent from the other curve points of the air/fuel ratio curve. As far as dual fuel burners, the ignition point set for the gas operation does not depend on the one set for the oil operation. LMV5x allow two different ignition position for gas mode and oil mode.
  • Page 58: Adjusting The Air/Fuel Ratio Curves

    9 ADJUSTING THE AIR/FUEL RATIO CURVES ATTENTION: when burners are provided with VSD, before setting the air/fuel ratio curves, the Standardization of the motor speed must be performed (see chapter “Standardization”). 1st level 2nd level 3rd level 4th level 5th level 6th level Description Params &...
  • Page 59: Setting The Load Points Output (Burners With No Fgr)

    Setting the load points output (burners with no FGR) Following the below route access to the programming levels of the menu 1st level 2nd level 3rd level 4th level 5th level 6th level Description Params & Display RatioControl Parameter settings for fuel/ air ratio control GasSettings Parameter settings for firing...
  • Page 60 Point Load To choose the actuator to set, press the “left arrow” and choose Air or VSD Fuel Point Load Press "Enter" to access the Air actuator value to be set. Fuel Point Load Press keys to change value. Fuel Point Load Press Enter...
  • Page 61 Caution! In case it is necessary to immediately shut the burner down while working at high flame and the maximum load point is not already set observing the combustion parameters, decrease gas by means of the pressure governor as to drive the burner to a sufficient excess of air, then shut the burner down by the main switch.
  • Page 62: Configurations For Burner With Fgr

    10 Configurations for burner with FGR 10.1 Recommendations Note! Reduction of maximum burner output Use of the flue gas recirculation (FGR) function or the flue gas mass introduced to the supply air duct might lower the burner’s maximum output. This means that the maximum amount of combustion air that can be introduced will be reduced. It is recommended to consider a proper air excess during the regulation of the burner in order to have to the right O2 content in the smoke, after the flue gas recirculation.
  • Page 63: Address And Activate The Aux3 Servomotor

    10.2 Address and activate the AUX3 servomotor. Usually these operations are already set in the manufacturer factory. They would be necessary in same cases as: the substitution of the servomotor, in case the FGR mode were not activated yet or the LMV5x were be supplied loose…...
  • Page 64: Setting The Special Positions

    10.3 Setting the special positions 1st level 2nd level 3rd level 4th level 5th level 6th level Description Param & Display RatioControl GasSettings OilSettings SpecialPosition Suggested positions are below. They can be modify during the commissioning according to right needs. Special Position: AUX3 POS •...
  • Page 65: Fgr Mode Choice

    10.5 FGR mode choice 1st level 2nd level 3rd level 4th level 5th level 6th level Description Param & Display Flue Gas Recirc According to the preference and FGR-Mode AUX3onCurve instruction in the table below. time temperature temp. contr. TCautoDeact deactMinpos auto deact Description of the FGR mode.
  • Page 66: Main Parameter Of The Fgr Function

    10.6 Main parameter of the FGR function LMV50 LMV52.4.. Parameter Description LMV51.3 LMV52.2 DelaytimeFGR Gas Setting of delay time for auxiliary actuator 3 to be kept in the ignition position after entering phase ● ● OPERATION DelaytimeFGR Oil ThresholdFGR Gas Setting of temperature that must not be exceeded so that auxiliary actuator 3 can be kept in the ●...
  • Page 67: Example Of Fgr Factor And Fgr Maps Factor On The Burner Regulation

    10.7 Example of FGR factor and FGR Maps Factor on the burner regulation. We consider to set the AUX3 for FGR with the “temp.contr.” Mode The curve is as per the below table. Point Note Load % 37,5 % 62,5 % 75 % 100 % AUX3 FGR Curve...
  • Page 68: Cold Start Thermal Shock (Cstp)

    11 Cold start thermal shock (CSTP) If there is a steam boiler or a boiler that must start up cold in the plant and to avoid thermal shocks a slow heating is required for the boiler by maintaining the burner at the minimum output, the automatic function “Cold start thermal shock” can be performed instead of the manual operation at minimum load. The CSTP (Cold Start Thermal Schock) function can be enabled by the Technical service only (access by reserved password).
  • Page 69 Note: by enabling the manual operation (this function can be set at user level also -see chapter “manual operation”) the CSTP function is momentary excluded, when enabling the automatic operation again, the CSTP function (previously set at Service level) will be enabled as well.
  • Page 70: Burner Manual Operation

    12 BURNER MANUAL OPERATION The operator can decide if choosing burner manual operation at a settable fixed load or modulating operation through the automatic load controller, then can also set the burner shutdown by means of the “burner off” function. Choose the type of operation (Au-tom / Manual / Off).
  • Page 72 Terminal Description of connection termi- nals group Connection symbol Electrical rating PIN1 Fan motor contactor AC 230 V +10 % / -15 %, 50...60 Hz, 1 A, cos.0.4 PIN2 Alarm AC 230 V +10 % / -15 %, 50...60 X3-01 Hz, 1 A, cos.0.4 PIN1 Air pressure switch (LP)
  • Page 73 Terminal Connection symbol Description of connection terminals Electrical rating group PIN1 Protective earth (PE) Pressure switch min-oil (DWmin-oil) AC 230 V +10 % / -15 %, PIN2 50...60 Hz, Imax 1.5 mA X5-01 Power signal for pressure switch-min- AC 230 V +10 % / -15 %, oil (DWmin-oil) PIN3 50...60 Hz, Imax 500 mA...
  • Page 74 Terminal Connection symbol Description of connection termi- nals Electrical rating group PIN1 Protective earth (PE) PIN2 Neutral conductor (N) X7-01 PIN3 Fuel valve 2 (oil) AC 230 V +10 % / -15 %, 50...60 Hz, 1 A, cos.0.4 PIN1 Protective earth (PE) PIN2 Neutral conductor (N) AC 230 V +10 % / -15 %, 50...60...
  • Page 75 Terminal Connection symbol Description of connection termi- nals Electrical rating group AC 230 V +10 % / -15 %, 50...60 PIN2 Firing on oil Hz, 1 A, cos.0.4 X8-01 PIN1 Firing on gas AC 230 V +10 % / -15 %, 50...60 Hz, 1 A, cos.0.4 PIN4 Protective earth (PE)
  • Page 76 Termi- nal group Connection symbol Description of connection termi- nals Electrical rating AC 230 V +10 % / -15 %, 50...60 Hz, PIN4 Neutral conductor (N) max 1 mA PIN3 Power signal transformer AC 12 V +10 % / -15 %, 50...60 Hz, X10-01 PIN2 AC power signal GO...
  • Page 77 (functional earth) PIN4 AC power supply from transformer to LMV5... system PIN3 AC 12 V +10 % / -15 %, 50...60 Hz PIN2 Reference ground (PELV) AC power supply from transformer to LMV5... system PIN1 AC 12 V +10 % / -15 %, 50...60 Hz Terminal Connection symbol Description of connection termi- nals...
  • Page 80 Note: Specifications and data subject to change. Errors and omissions excepted.
  • Page 81 COD. M07979CD rel. 3.2 01/13 RECOMMENDATIONS FOR LMV5x CONNECTIONS Connections affected by EMC noises are related to the bus cable (actuator line cable, PLL52), detection probe cable, speed sensor cable, 4-20mA signal cable that controls the VSD. Input and power cables (400V e 230V) must be laid separately from the signal cables. The bus cable between control panel and burner and between burner and PLL52 board (used when O2 trim control must be perfomed) must be laid separately and far from power cables.
  • Page 82 Annex1 – Example for motor cable...
  • Page 84 Annex 2 – Example for sensor cable...
  • Page 87 SIEMENS Appendix: Example for wiring, earthing and shielding the LMV5-System Cabinet Siemens MM440 CAN-Bus shielded cable X52.2 X52.4 "VSD - Fan Motor" Separate conduit & shielded line voltage cable! Separate plastic conduit X51, X50 Metal plate = FE for high voltage ign. cable X9-02 X10-01 Power...
  • Page 88 Addendum 4: LMV52... with O trim control and O module General The LMV52... system is an extended LMV51... system. A special feature of the LMV52… is control of the residual oxygen content to increase the boiler’s efficiency. In addition to the features of the LMV51..., the LMV52... provides O trim control, con- trol of a maximum of 6 actuators, control of a VSD, and acquisition of cumulated fuel consumption and current fuel throughput.
  • Page 89 The maximum cable length between transformer and CAN bus users is dependent on Determination of the the type of cable (cross-sectional area), the number of actuators and the type of actua- maximum cable length tor used (current). The following graphs can be used to determine the maximum CAN bus cable lengths between the transformer and group of actuators or the AZL5…, depending on the rele- vant influencing factors.
  • Page 91 Example 2 LMV5... basic unit in the control panel, actuator on the burner; CAN bus cable «LMV5... → SA» > 20 m Jumper Control panel Burner ACT 1 ACT 2 ACT 3 ACT 4 Fixed internal bus termination SQM4... SQM4... SQM4...
  • Page 92 Example 3a Installation of all components in the burner; CAN bus cable «LMV52... ↔ SA» > 20 m with 6 actuators and O2 module PLL52... Jumper Fixed internal ACT 1 ACT 2 ACT 3 ACT 4 ACT 5 ACT 6 bus termination SQM45...
  • Page 93 Notes on example 3a / 3b CAN bus cable with LMV52... and more than 4 actuators and O2 module PLL52... On LMV52... applications with more than 4 actuators (SQM45...), a second transformer is required for powering the extra actuators. In that case, transformer 1 powers the LMV52... basic unit, the AZL5..., and the first 4 actuators.
  • Page 94 O2 module In comparison with the LMV51... system, the extra components to be connected with the LMV52… system are the O module and the O sensor QGO... and, optionally, the combustion air and flue gas temperature sensors. The O module is to be connected to the basic unit via the CAN bus.
  • Page 96      8      8      8...
  • Page 97 ß ß ß...
  • Page 98 ©...
  • Page 99 Technical Data PLL52... LMV52... basic unit Refer to chapter Technical Data! Mains voltage «X89-01» AC 120 V AC 230 V PLL52... –15 % / +10 % -15 % / +10 % Safety class I with parts according to II as per DIN EN 60730-1 Mains frequency 50 / 60 Hz ±6 % Power consumption...
  • Page 100 PLL52... Flue gas temperature X86.3 Shield connection Temperature sensor X86.1 Pt / LG-Ni1000 PLL52... Pt / LG-Ni1000 X86.2 Signal reference X89-01.4 Protective earth (PE) Supply air temperature X89-01.5 Power supply neutral X87.3 conductor (L) Shield connection F 6.3AT Temperature sensor X87.1 X89-01.6 Power supply live Pt / LG-Ni1000...
  • Page 101 KOSTAL INVERTER Connection and programming for electronically controlled burners with LMV2x/3x, LMV5x, ETAMATIC and INVERTER regulation Service Manual TECHNICAL INSTRUCTIONS M12938CA - Rel. 0 - 10/2021...
  • Page 102 Table of contents: INVERTER identification, 3 User interface communication (on request), 4 Electrical connections, 5 Motor connection variants for INVERTERS sizes A, B and C, 5 Motor connection variants for INVERTER size D, 6 Connection of INVERTER signals and commands, 7 Electrical connections and parameter configuration, 7 0-10V / 4-20mA analogue input configuration, 8 Configuration of control contact / INVERTER starting and stopping, 9...
  • Page 103: Inverter Identification

    IDENTIFICAZIONE INVERTER INVEOR Mx IVxx PWxx LPxx APxx GHxx DKxx COxx 1 Application circuit board: Drive controller series: INVEOR AP12 - Standard AP13 - CANopen Control: Installation location/size: motor-integrated - M, size: α, A, DK01 - Standard (without membrane keypad) B, C, D DK04 –...
  • Page 104: User Interface Communication (On Request)

    User interface COMMUNICATION (on request) The drive controller can be put in operation in the following ways: Attention: Contact the manufacturer to order the most suitable device. USB adaptor for PC Via the INVERTER PC software INVEOR MMI remote display: INVEOR MMI is a portable display on which all inverter parameters can be viewed and changed.
  • Page 105: Electrical Connections

    ELECTRICAL CONNECTIONS Motor connection variants for INVERTERS sizes A, B and C Star or delta connection for speed controller integrated on the motor Delta connection variant Star connection variant Nut MA = 5 Nm Circlip Plain washer Cable shoe Fig. 1...
  • Page 106: Motor Connection Variants For Inverter Size D

    Motor connection variants for INVERTER size D X1 terminal no. Designation Assignment Mains phase 1 Mains phase 2 Mains phase 3 Protective conductor Tab. 1 - X1 terminal assignment - 3 x 400 VAC X4 terminal no. Designation Assignment Protective conductor Mains phase 1 Mains phase 2 Mains phase 3...
  • Page 107: Connection Of Inverter Signals And Commands

    Connection of INVERTER signals and commands Input signal 4 ÷ 20 mA / 0 ÷ 10 V START INVERTER Jump er 5- Electrical connections and parameter configuration There are 2 relays on the INVERTER. Connecting terminals X7-1-2-3 and X6-1-2-3 are used for: LMV2/3x: Relay 1 is used as a safety contact on the safety loop series of the equipment.
  • Page 108: 0-10V / 4-20Ma Analogue Input Configuration

    0-10V / 4-20mA analogue input configuration Input signal 4 ÷ 20 mA / 0 ÷ 10 V Input AIn1 can be configured as voltage or current input. It is configured as 4‐20mA input current for LMV5‐Etamatic, and 0‐10V input voltage for LMV2x/3x. Specifies the input type, whether voltage or current.
  • Page 109: Configuration Of Control Contact / Inverter Starting And Stopping

    Configuration of control contact / INVERTER starting and stopping START INVERTER Jump er 5- Terminal Bringing 24V to terminal X5‐6 enables INVERTER operation and the contact that switches it on/off. X5‐3 (24V Out)… X5‐6 (Digit In1).. On LMV2/3x X5‐3 (24V Out) also powers the motor speed encoder.
  • Page 110: Configuration Of Inverter Start / Stop Parameters And Operating Mode

    Configuration of INVERTER start / stop parameters and operating mode Parameter Minimum input frequency in Hz. 1.020 Min. frequency (Hz) Set value = 0 Hz (LMV2x-3x / LMV5x) Set value = > 35 Hz (ETAMATIC) Maximum input frequency in Hz. 1.021 Max.
  • Page 111: Motor Data

    Motor data The motor data depend on the type of motor used. Refer to the data shown on the motor nameplate. Follow the steps below: - Enter the motor data; - Activate the motor recognition function; - If the operation ends successfully, enter the remaining parameters. During the recognition phase, the INVERTER measures some parameters and changes some settings.
  • Page 112: Output Signal Variant For Reading Motor Rpm (Optional)

    Activate the “Motor identification” function and follow the instructions proposed by the INVERTER, then change the parameters described below. The image shows the software screen on the PC. Parameter Open-loop asynchronous motor. 34.010 Control type Set value = 100 (open-loop asynchronous motor) 34.020 Flying restart Set value = 1 (enabled) Calculated by Inverter.
  • Page 113 NOTE If the system enters pendulum mode with LMV.. / ETAMATIC, adjust parameters 34.090 and 34.091 by increasing them, in particular parameter 34.090, in steps of 100mA/rad/sec. With LMV 2x/3x with INVERTER control, the device controls the standby rpm with param. 653. If, after the fan is switched off, the device LMV 2x/3x sees that the motor continues to run, error 83 diagnostic 32 NOTE appears.
  • Page 114: Brake Chopper Connections

    Brake chopper connections Braking resistor connection terminal Brake chopper connections Terminal no. Designation Assignment Braking resistor connection (+) Braking resistor connection (-) Optional assignment of brake chopper Parameter Braking resistor Enabled or disabled Braking resistors...
  • Page 115 Burner terminal block with interface INVERTER Versioni bruciatore con LMV2x/3x Connection to braking resistors when fitted Single-sided shielding LMVxx INVEOR Mx-xxxx-xxxx - LP02/LP04-... Versioni bruciatore con LMV5x o ETAMATIC Connection to braking resistors when fitted Single-sided shielding LMVxx LMV5x / ETAMATIC INVEOR Mx-xxxx-xxxx - LP02/LP04-...
  • Page 116: Burner Terminal With Inverter Interface

    C.I.B. UNIGAS S.p.A. Via L.Galvani, 9 - 35011 Campodarsego (PD) - ITALY Tel. +39 049 9200944 - Fax +39 049 9200945/9201269 web site: www.cibunigas.it - e-mail: cibunigas@cibunigas.it Note: specifications and data subject to change. Errors and omissions excepted.