4 MONITORING SPECIFICATION

4.6.5 Random write command

(1) Random write command
(2) Command format
(3) Communication overview
4 - 22
This is a command to write remote register data to several different GOT internal
devices.
Transfer Direction
RWwm (Higher byte)
RWwm (Lower byte)
RWwm + 1
Master station
GOT
RWwm + 2
RWwm + 3 to RWwn + E
RWwn + F
GOT
Master station RWrn to RWrn + F
When writing remote register data to the GOT internal device GD100, 200, and
300 (3points)
PLC CPU
TO
1) Store the random write command data in the master station's remote register
(RWw).
2) Turn on the GOT request flag, and store the command data in the GOT
remote register (RWw). Store the write data in GD100, 200, and 300.
(Command execution)
The GOT complete flag turns on when the command processing is complete.
Get other manuals https://www.bkmanuals.com
Addresses
5: Random write setting
When the occupied points are 2 stations
1 to 3 :Points to be written to the GOT internal device
When the occupied points are 4 stations
1 to 7 :Points to be written to the GOT internal device
0 to 1023 : GOT internal device numbers to be
written
Stores the data to be written to the GOT internal device
described above
Stores the data to be written and GOT internal device
numbers for the setting points like mentioned above.
Master station
remote register
RWw0
0503
H
RWw1
0064
H
RWw2
1234
H
1)
RWw3
00C8
H
RWr4
0E54
H
RWr5
012C
H
RWr6
0066
H
MELSEC-GOT
Write data
———
———
GOT
remote register
RWw0
0503
H
RWw1
0064
H
RWw2
1234
H
2)
RWw3
00C8
H
RWr4
0E54
H
RWr5
012C
H
RWr6
0066
H
2)
GD100
1234
H
GD200
0E54
H
GD300
0066
H
GOT internal device
4 - 22

Advertisement

Table of Contents
loading

This manual is also suitable for:

900 seriesA8gt-j61bt15A8gt-j61bt13

Table of Contents