19.3.2

Faulty merging unit for bay in service

When a merging unit goes faulty while the bay is in service, the protection functions connected to that
merging unit get blocked. Also, protection functions configured in a 1 1/2 circuit breaker applications,
where two SV streams from different merging units are combined get blocked. Thus, this has no effect on
protection functions in a 1 1/2 circuit breaker configuration.
This can be resolved by connecting external binary input signals to the BLOCK input on the respective
SMAI function blocks with the use of ACT. When the BLOCK input on a SMAI function is energized, the
280