Hitachi Relion 670 Series Applications Manual page 52

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 4
Analog inputs
ANSI06000196 V1 EN-US
Figure 10:
For busbar protection, it is possible to set the CT_WyePoint parameters in two ways.
The first solution will be to use busbar as a reference object. In that case for all CT inputs marked with 1
in Figure 10, set CT_WyePoint = ToObject, and for all CT inputs marked with 2 in Figure 10, set
CT_WyePoint = FromObject.
The second solution will be to use all connected bays as reference objects. In that case for all CT inputs
marked with 1 in Figure 10, set CT_WyePoint = FromObject, and for all CT inputs marked with 2 in
Figure 10, set CT_WyePoint = ToObject.
Regardless which one of the above two options is selected, busbar differential protection will behave
correctly.
The main CT ratios must also be set. This is done by setting the two parameters CTsec and CTprim for
each current channel. For a 1000/5 A CT, the following settings shall be used:
46
Example how to set CT_WyePoint parameters in the IED
© 2017 - 2023 Hitachi Energy. All rights reserved
Busbar
Busbar
Protection
1
2
1MRK511407-UUS Rev. N
2
1
en06000196_ansi.vsd
Phasor measurement unit RES670
Application manual