1MRK511407-UUS Rev. N
Table 21:
Set value for parameter
"CurrentInput"
1
PhaseA
2
PhaseB
3
PhaseC
4
PosSeq
5
NegSeq
6
3 · ZeroSeq
7
MaxPh
8
MinPh
9
UnbalancePh
10
PhaseA-PhaseB
11
PhaseB-PhaseC
12
PhaseC-PhaseA
13
MaxPh-Ph
14
MinPh-Ph
15
UnbalancePh-Ph
The user can select a voltage input, by a setting parameter VoltageInput, to measure one of the voltage
quantities shown in table 22.
Table 22:
Set value for parameter
"VoltageInput"
1
PhaseA
2
PhaseB
3
PhaseC
4
PosSeq
5
-NegSeq
Table continues on next page
Phasor measurement unit RES670
Application manual
Available selection for current quantity within CVGAPC function
Comment
CVGAPC function will measure the phase A current phasor
CVGAPC function will measure the phase B current phasor
CVGAPC function will measure the phase C current phasor
CVGAPC function will measure internally calculated positive sequence current
phasor
CVGAPC function will measure internally calculated negative sequence current
phasor
CVGAPC function will measure internally calculated zero sequence current phasor
multiplied by factor 3
CVGAPC function will measure current phasor of the phase with maximum
magnitude
CVGAPC function will measure current phasor of the phase with minimum
magnitude
CVGAPC function will measure magnitude of unbalance current, which is internally
calculated as the algebraic magnitude difference between the current phasor of the
phase with maximum magnitude and current phasor of the phase with minimum
magnitude. Phase angle will be set to 0° all the time
CVGAPC function will measure the current phasor internally calculated as the vector
difference between the phase A current phasor and phase B current phasor (VA-VB)
CVGAPC function will measure the current phasor internally calculated as the vector
difference between the phase B current phasor and phase C current phasor (VB-
VC)
CVGAPC function will measure the current phasor internally calculated as the vector
difference between the phase C current phasor and phase A current phasor ( VC-
VA)
CVGAPC function will measure ph-ph current phasor with the maximum magnitude
CVGAPC function will measure ph-ph current phasor with the minimum magnitude
CVGAPC function will measure magnitude of unbalance current, which is internally
calculated as the algebraic magnitude difference between the ph-ph current phasor
with maximum magnitude and ph-ph current phasor with minimum magnitude.
Phase angle will be set to 0° all the time
Available selection for voltage quantity within CVGAPC function
Comment
CVGAPC function will measure the phase A voltage phasor
CVGAPC function will measure the phase B voltage phasor
CVGAPC function will measure the phase C voltage phasor
CVGAPC function will measure internally calculated positive sequence voltage
phasor
CVGAPC function will measure internally calculated negative sequence voltage
phasor. This voltage phasor will be intentionally rotated for 180° in order to enable
easier settings for the directional feature when used.
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11
Multipurpose protection
171