Hitachi Relion 670 Series Applications Manual page 242

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 16
Monitoring
Setting
k
VGenZeroDb
IGenZeroDb
VBase (set in
Global base)
IBase (set in
Global base)
SBase (set in
Global base)
Table 30:
Setting
PMin
PMax
PZeroDb
PRepTyp
PDbRepInt
PHiHiLim
PHiLim
PLowLim
PLowLowlLim
PLimHyst
Table 31:
Setting
IMagComp5
IMagComp30
IMagComp100
VAmpComp5
Table continues on next page
236
Short Description
Low pass filter coefficient for
power measurement, V and I
Zero point clamping in % of
Ubase
Zero point clamping in % of Ibase 3
Base setting for voltage level in
kV
Base setting for current level in A
Base Setting for power base in
MVA
Settings parameters for level supervision
Short Description
Minimum value
Minimum value
Zero point clamping in 0.001% of
range
Reporting type
Cycl: Report interval (s), Db: In
0.001% of range, Int Db: In
0.001%s
High High limit (physical value), %
of SBase
High limit (physical value), in % of
SBase
Low limit (physical value), in % of
SBase
Low Low limit (physical value), in
% of SBase
Hysteresis value in % of range
(common for all limits)
Settings for calibration parameters
Short Description
Magnitude factor to calibrate
current at 5% of In
Magnitude factor to calibrate
current at 30% of In
Magnitude factor to calibrate
current at 100% of In
Magnitude factor to calibrate
voltage at 5% of Vn
© 2017 - 2023 Hitachi Energy. All rights reserved
Selected
Comments
value
0.00
Typically no additional filtering is required
25
Set minimum voltage level to 25%. Voltage below 25%
will force S, P and Q to zero.
Set minimum current level to 3%. Current below 3%
will force S, P and Q to zero.
400.00
Set rated OHL phase-to-phase voltage
1000
Set rated primary CT current used for OHL
1000
Set based on rated Power
Selected
Comments
value
-100
Minimum expected load
100
Maximum expected load
3000
Set zero point clamping to 60 MW that is, 3% of 200
MW
db
Select magnitude deadband supervision
2000
Set ±Δdb=40 MW that is, 2% (larger changes than 40
MW will be reported)
60
High alarm limit that is, extreme overload alarm, hence
it will be 415 MW.
50
High warning limit that is, overload warning, hence it
will be 371 MW.
-50
Low warning limit -500 MW
-60
Low alarm limit -600 MW
1
Set ±Δ Hysteresis 20 MW that is, 1% of range (2000
MW)
Selected
Comments
value
0.00
0.00
0.00
0.00
1MRK511407-UUS Rev. N
Phasor measurement unit RES670
Application manual