For each of them detail explanation and final list of selected setting parameters values will be provided.
Measurement function application for a 380kV OHL
Single line diagram for this application is given in figure 98:
800/5 A
380kV 120V
/
3
ANSI09000039 V1 EN-US
Figure 98:
In order to monitor, supervise and calibrate the active and reactive power as indicated in figure
necessary to do the following:
1.
Set correctly CT and VT data and phase angle reference channel PhaseAngleRef using PCM600 for
analog input channels
2.
Connect, in PCM600, measurement function to three-phase CT and VT inputs
3.
Set under General settings parameters for the Measurement function:
Table 29:
Setting
Operation
PowAmpFact
PowAngComp
Mode
Table continues on next page
Phasor measurement unit RES670
Application manual
The available measured values of an IED are depending on the actual hardware (TRM) and
the logic configuration made in PCM600.
380kV Busbar
kV
3
P
Q
380kV OHL
Single line diagram for 380kV OHL application
general settings as shown in table 29.
level supervision of active power as shown in table 30.
calibration parameters as shown in table 31.
General settings parameters for the Measurement function
Short Description
Operation Off/On
Amplitude factor to scale power
calculations
Angle compensation for phase
shift between measured I & U
Selection of measured current
and voltage
© 2017 - 2023 Hitachi Energy. All rights reserved
IED
ANSI09000039-1-en.vsd
Selected
Comments
value
On
Function must be On
1.000
It can be used during commissioning to achieve higher
measurement accuracy. Typically no scaling is required
0.0
It can be used during commissioning to achieve higher
measurement accuracy. Typically no angle
compensation is required. As well here required
direction of P & Q measurement is towards protected
object (as per IED internal default direction)
L1, L2, L3
All three phase-to-ground VT inputs are available
Section 16
Monitoring
SEMOD54481-12 v11
98
it is
235