Wide Area Measurement System; Protocol Reporting Via Ieee 1344 And Iec/Ieee 60255-118 (C37.118) Pmureport; Identification; Application - Hitachi Relion 670 Series Applications Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK511407-UUS Rev. N
Section 6
6.1
Protocol reporting via IEEE 1344 and IEC/IEEE 60255-118
(C37.118) PMUREPORT
6.1.1

Identification

Function description
Protocol reporting via IEEE 1344 and
C37.118
6.1.2

Application

The phasor measurement reporting block moves the phasor calculations into an IEC/IEEE 60255-118
(C37.118) and/or IEEE 1344 synchrophasor frame format. The PMUREPORT block contains parameters
for PMU performance class and reporting rate, the IDCODE and Global PMU ID, format of the data
streamed through the protocol, the type of reported synchrophasors, as well as settings for reporting
analog and digital signals.
The message generated by the PMUREPORT function block is set in accordance with the IEC/IEEE
60255-118 (C37.118) and/or IEEE 1344 standards.
There are settings for Phasor type (positive sequence, negative sequence or zero sequence in case of 3-
phase phasor and A, B or C in case of single phase phasor), PMU's Service class (Protection or
Measurement), Phasor representation (polar or rectangular) and the data types for phasor data, analog
data and frequency data.
Synchrophasor data can be reported to up to 8 clients over TCP and/or 6 UDP group clients for multicast
or unicast transmission of phasor data from the IED. More information regarding synchrophasor
communication structure and TCP/UDP configuration is available in section
(C37.118) Phasor Measurement Data Streaming Protocol
Multiple PMU functionality can be configured in the IED, which can stream out same or different data at
different reporting rates or different performance (service) classes. There are 2 instances of PMU
functionality available in the IED. Each instance of PMU functionality includes a set of PMU reporting
function blocks tagged by the same instance number (1 or 2). As shown in the following figures, each set
of PMU reporting function blocks includes PMUREPORT, PHASORREPORT1-4, ANALOGREPORT1-3,
and BINARYREPORT1-3 function blocks. In general, each instance of PMU functionality has 32
configurable phasor channels (PHASORREPORT1–4 blocks), 24 analog channels
(ANALOGREPORT1-3 blocks), and 28 digital channels (24 digital-report channels in
BINARYREPORT1-3 and 4 trigger-report channels in PMUREPORT function block). Special rules shall
be taken into account in PCM600 for Application Configuration and Parameter Settings of multiple
PMUREPORT blocks. These rules are explained in the the Application Manual in section
Function Blocks Connection
Figure
32
instance has 4 predefined binary input signals corresponding to the Bits 03-00: Trigger Reason defined in
STAT field of the Data frame in IEC/IEEE 60255-118 (C37.118) standard. These are predefined inputs for
Frequency Trigger, Rate of Change of Frequency trigger, Magnitude High and Magnitude Low triggers.
Phasor measurement unit RES670
Application manual

Wide area measurement system

Rules.
shows both instances of the PMUREPORT function block. As seen, each PMUREPORT
© 2017 - 2023 Hitachi Energy. All rights reserved
IEC 61850
IEC 60617
identification
identification
PMUREPORT
-
Configuration.
Wide area measurement system
GUID-0C45D2FA-1B95-4FCA-B23B-A28C2770B817 v2
GUID-0090956B-48F1-4E8B-9A40-90044C71DF20 v1
ANSI/IEEE C37.2
device number
-
GUID-8DF29209-252A-4E51-9F4A-B14B669E71AB v5
IEC/IEEE 60255-118
PMU Report
Section 6
77

Advertisement

Table of Contents
loading

This manual is also suitable for:

Res670

Table of Contents