Hitachi Relion 670 Series Applications Manual page 234

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 15
Logic
If the comparison should be done between two current magnitudes then those current signals need to be
connected to function inputs, INPUT and REF. Then the settings should be adjusted as below,
EnaAbs = Absolute
RefSource = Input REF
EqualBandHigh = 5.0 % of reference value
EqualBandLow = 5.0 % of reference value.
228
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK511407-UUS Rev. N
Phasor measurement unit RES670
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Res670

Table of Contents