Test
IEC
61000-4-9
IEC
61000-4-11
IEC
61000-4-16
IEC
61000-4-17
IEC
61000-4-18
IEC
61000-4-29
IEC
60255-27
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RSG907R meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
RUGGEDCOM RSG907R
Installation Manual, 02/2021, C79000-G8976-1387-12
All manuals and user guides at all-guidesbox.com
Description
Pulse Magnetic Field
Voltage Dips and Interrupts
Mains Frequency Voltage
Ripple on DC Power Supply
Damped Oscillatory Wave
Voltage Dips and Interrupts
Dielectric Strength
HV Impulse
Test
IEEE 1613
ESD
IEEE 1613
Radiated RFI
IEEE 1613
Fast
Transient
6.2 EMC and Environmental Type Tests
Test Levels
Enclosure
300 A/m
Ports
AC Power
30% for 0.5 Cycles
Ports
60% for 5 Cycles
100% for 250 Cycles
Signal Ports
30 V Continuous
300 V for 1 s
DC Power
30 V Continuous
Ports
300 V for 1 s
DC Power
15%
Ports
Slow
2.5 kV Common
Damped
100 kHz or 1 MHz
DC Power
30% for 0.1 s
Ports
60% for 0.1 s
100% for 0.05 s
Signal Ports
2 kV (Failsafe Relay Output)
DC Power
2 kV or 2.8kV DC
Ports
AC Power
2 kV
Ports
Signal Ports
5 kV (Failsafe Relay Output)
DC Power
5 kV
Ports
AC Power
5 kV
Ports
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Certification
Severity
Levels
4
 
4
4
4
3
 
 
 
 
 
 
 
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV