Approvals Information - Omega CN8EPt User Manual

Table of Contents

Advertisement

TM
PLATINUM
Series Controllers User's Guide
10.

Approvals Information

This product conforms to the EMC: 2014/30/EU (EMC Directive).
Electrical Safety: 2014/35/EU (Low Voltage Directive)
Safety requirements for electrical equipment for measurement, control, and laboratory
Double Insulation; Pollution Degree 2
Dielectric withstand Test per 1 min
Power to Input/Output:
Power to Input/Output
Power to Relays/SSR Output: 2300 Vac (3250 Vdc)
Ethernet to Inputs:
Isolated RS232 to Inputs:
Isolated Analog to Inputs:
Analog/Pulse to Inputs:
Measurement Category I
Category I includes measurements performed on circuits not directly connected to the Mains Supply
(power). Maximum Line-to-Neutral working voltage is 50Vac/dc. This unit should not be used in
Measurement Categories II, III, and IV.
Transients Overvoltage Surge (1.2 / 50uS pulse)
Input Power:
3
Input Power
:
Ethernet:
Input/Output Signals:
ADDITIONAL INFORMATION:
FCC: This device complies with Part 15, Subpart B, Class B of the FCC rules, for option –EIP only.
RoHS II: The above product has been declared by the original supplier as Compliant. The manufacturer
of this item declares that the product complies with the EEE RoHS II Directive 2011/65/EC.26
UL File Number: E209855
2
Low-voltage DC power option: Units configured for external low power DC voltage, 12–36Vdc.
3
Ibid.
M5451
2300 Vac (3250 Vdc)
2
:
1500 Vac (2120 Vdc)
1500 Vac (2120 Vdc)
500 Vac
(720 Vdc)
500 Vac
(720 Vdc)
No Isolation
2500 V
1500 V
1500 V
500 V
Approvals Information
Omega Engineering | www.omega.com
77