Connecting Power - Omega CN8EPt User Manual

Table of Contents

Advertisement

TM
PLATINUM
Series Controllers User's Guide
Ethernet Connector if EIP
Option Installed
Figure 3 – CN16Pt and CN32Pt Models: Back Panel Connections

3.2 Connecting Power

Connect the main power connections to pins 7 and 8 of the 8-pin power / output connector as shown in
Figure
4.
110 ~ 300 Vdc
110 ~ 300 Vdc
Caution: Do not connect power to your device until you have completed all input
and output connections. Failure to do so may result in injury!
For the low-voltage power option, maintain the same degree of protection as the standard high-
voltage input power units (90–240 Vac) by using a Safety Agency Approved DC or AC source with
the same Overvoltage Category and pollution degree as the standard AC unit (90–300 Vac).
The Safety European Standard EN61010-1 for measurement, control, and laboratory equipment
requires that fuses must be specified based on IEC127. This standard specifies the letter code "T"
for a Time-lag fuse.
M5451
8-Pin Power / Outputs Connector
Ethernet Communications Status
LEDs if EIP Option Installed
Use Copper Conductors
rated for 75 C min
only for Power Connections
Figure 4 – Main Power Connections
Wiring Instructions
10-Pin Input Connector
USB Connector (on side,
cable stub shown)
Omega Engineering | www.omega.com
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cn32ptCn16ptCn16ptdCn8ptCn8ptdPlatinum series

Table of Contents