Navigate to the desired setting. Settings include the following:
ENbL – Enable sensor error latch. Manual intervention is required to clear the error.
dSbL – Disable sensor error latch. Unit automatically resumes if sensor errors are
cleared
Confirm the value.
6.7.7 Output Break detection (INIt > SFty > OUT.M > o.bRK)
Select the Output Break Detection (o.bRk) parameter. Output Break is detected when during
output saturation (i.e: PID is at 100%), the process value does not move the specified amount
of Process Deviation (P.dEV) in the specified amount of Time Deviation (T.dEV).
Navigate to the desired setting. Settings include the following:
ENbL – Enable Output break detection.
dSbL – Disable Output break detection
P.dEV – Process Deviation condition (in process units)
T.dEV – Time Deviation condition (in minutes)
Confirm the value.
6.7.8 Output Error Latch (INIt > SFty > OUT.M > E.LAT)
Select the Error latch (E.LAT) parameter. When E.LAT is enabled, if any output error is
detected (output break detection), the unit will be put in fault mode. Manual intervention is
required to clear the error. When E.LAT is disabled, if the fault conditions no longer exist, the
unit will resume its previous running state.
Navigate to the desired setting. Settings include the following:
ENbL – Enable sensor error latch. Manual intervention is required to clear the error.
dSbL – Disable sensor error latch. Unit automatically resumes if sensor errors are
cleared
Confirm the value.
6.8 Manual Temperature Calibration (INIt > t.CAL)
Select the Manual Temperature Calibration (t.CAL) submenu. This parameter allows manual
adjustment to the thermocouple, RTD, or Thermistor calibration curves provided with the
unit. Once a curve has been manually adjusted, this setting can be set to NoNE to disable the
manual adjustment (resetting to factory defaults will remove any manually adjustment
factors).
Navigate to the desired setting. Settings include:
NoNE – No manual calibration (factory default)
1.PNt – Manually create a 1-point calibration
2.PNt – Manually create a 2-point calibration
ICE.P – Manually create a 1-point calibration at 0
Select the indicated option.
M5451
Reference Section: Initialization Mode (INIt)