Absolute Or Deviation Alarm (Prog > Alm.1, Alm.2 > Type > Ab.dv); Alarm High Reference (Prog > Alm.1, Alm.2 > Type > Alr.h) - Omega CN8EPt User Manual

Table of Contents

Advertisement

TM
PLATINUM
Series Controllers User's Guide
Setting
Absolute (AbSo)
AboV
> ALR.H
bELo
< ALR.L
HI.Lo.
< ALR.L or > ALR.H
bANd
> ALR.L and < ALR.H
Absolute Mode (AbSo)
Deviation Mode (dEVI)
7.3.2 Absolute or Deviation Alarm (PRoG > ALM.1, ALM.2 > tyPE >
Ab.dV)
Select the Absolute or Deviation Alarm (Ab.dV) parameter.
Navigate to the correct setting. Settings and sub settings include the following:
AbSo – Alarm is triggered using calculations based on the absolute values of ALR.H
or ALR.L used as specified by the tyPE parameter
d.SP1 – Alarm is triggered using calculations based on values relative to SP1 as
specified by the tyPE parameter
d.SP2 – Alarm is triggered using calculations based on values relative to SP2 as
specified by the tyPE parameter.
CN.SP – Alarm is triggered using calculations based on values relative to
instantaneous control setpoint generated by Ramp & Soak as specified by the tyPE
parameter.
Select the desired setting.
7.3.3 Alarm High Reference (PRoG > ALM.1, ALM.2 > tyPE > ALR.H)
Select the Alarm High Reference (ALR.H) parameter.
Set the Alarm High Reference value.
Confirm the value.
M5451
Table 7 – Alarm Range Option Comparison
Deviation (d.SP1)
> SP1 + ALR.H
< SP1 - ALR.L
< SP1 - ALR.L or > SP1 + ALR.H
> SP1 - ALR.L and < SP1 + ALR.H
ALR.L
bELo, HI.Lo.
Lower
bANd
bELo, HI.Lo.
ALR.L
Lower
Figure 10 – Alarm Range Option Diagram
Reference Section: Programming Mode (PRoG)
Deviation (d.SP2)
> SP2 + ALR.H
< SP2 - ALR.L
< SP2 - ALR.L or > SP2 + ALR.H
> SP2 - ALR.L and < SP2 + ALR.H
ALR.H
bANd
SP1
AboV, HI.Lo.
ALR.H
Omega Engineering | www.omega.com
50
AboV, HI.Lo.
Higher
SP2
(SP2 has the same
alarm options.)
Higher

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cn32ptCn16ptCn16ptdCn8ptCn8ptdPlatinum series

Table of Contents