Omega CN8EPt User Manual page 62

Table of Contents

Advertisement

TM
PLATINUM
Series Controllers User's Guide
If oN, navigate to the desired input range. Options include the following:
4–20 – 4.00–20.00 mA input signal range
0–24 – 0.00–24.00 mA input signal range
0–10 – 0.00–10.00 V input signal range
0–1 – 0.00–1.00 V input signal range
Select the desired input signal range to proceed to the scaling parameters starting with RS.Lo.
Navigate to the desired setting. Settings include the following:
RS.Lo – Minimum Setpoint value (entry point). Setpoint 1 is set to this value when
the analog input signal is IN.Lo.
IN.Lo – Input value in mA or V for RS.Lo
RS.HI – Maximum Setpoint value. Setpoint 1 is set to this value when the analog
input signal is IN.HI.
IN.HI – Input value in mA or V for RS.HI
Select the indicated setting.
Set the desired value.
Confirm the value.
M5451
Reference Section: Programming Mode (PRoG)
Omega Engineering | www.omega.com
62