YASKAWA GA80U4720ABM Manual page 994

Table of Contents

Advertisement

12.11 o: Keypad-Related Settings
No.
Item
14
Reserved
15
Encoding data
16
File number
o5-01: Log Start/Stop Selection
No.
Name
(Hex.)
o5-01
Log Start/Stop Selection
(1551)
RUN
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in o5-02 [Log Sampling Interval].
o5-02: Log Sampling Interval
No.
Name
(Hex.)
o5-02
Log Sampling Interval
(1552)
RUN
o5-03: Log Monitor Data 1
No.
Name
(Hex.)
o5-03
Log Monitor Data 1
(1553)
RUN
Note:
Set the U monitor number you want to log.
For example, to display U1-01 [Frequency Reference], set o5-03 = 101. When it is not necessary to set a data log monitor, set this parameter
to 000.
o5-04: Log Monitor Data 2
No.
Name
(Hex.)
o5-04
Log Monitor Data 2
(1554)
RUN
Note:
Set the U monitor number you will log.
For example, to show U1-02 [Output Frequency], set o5-04 = 102. When it is not necessary to set data log monitor, set this parameter to
000.
994
Number of
Characters
4
-
4
Encoding data for log monitor data 1 through 10 (Hex.)
Bits 0 through 9 show the encoding of log monitor data 1 1 through 10. A bit value of 1 shows that the data represents a
negative value. (Log monitor data 1 through 10 is absolute value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7 have values of 1, and the encoding data
= 0010010010 (Bin.) = 0092 (Hex.)
6
Row number (Hex.) in the data log file
V/f
CL-V/f
OLV
CLV
Sets the data log function. This parameter is only available when using an LCD keypad.
V/f
CL-V/f
OLV
CLV
Sets the data log sampling cycle. This parameter is only available when using an LCD keypad.
V/f
CL-V/f
OLV
CLV
Sets the data log monitor. This parameter is only available when using an LCD keypad.
V/f
CL-V/f
OLV
CLV
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Description
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Default
(Range)
0
(0 - 1)
Default
(Range)
100 ms
(100 - 60000 ms)
Default
(Range)
101
(000, 101 - 999)
Default
(Range)
102
(000, 101 - 999)

Advertisement

Table of Contents
loading