YASKAWA GA80U4720ABM Manual page 1005

Table of Contents

Advertisement

T4-02: Motor Type Selection
No.
Name
(Hex.)
T4-02
Motor Type Selection
(3131)
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
T4-04: Motor Rated Revolutions
No.
Name
(Hex.)
T4-04
Motor Rated Revolutions
(3133)
T4-05: Motor Rated Frequency
No.
Name
(Hex.)
T4-05
Motor Rated Frequency
(3134)
Note:
When T4-02 = 1, 2 [Motor Type Selection = PM, SynRM], input is not necessary because it assumes: Motor Rated Revolutions/60 × Number
of Motor Poles/2.
T4-06: Motor Rated Voltage
No.
Name
(Hex.)
T4-06
Motor Rated Voltage
(3135)
T4-07: Motor Rated Current
No.
Name
(Hex.)
T4-07
Motor Rated Current
(3136)
Note:
The value set here becomes the base value for motor protection, the torque limit, and torque control.
T4-08: Motor Rated Capacity
No.
Name
(Hex.)
T4-08
Motor Rated Capacity
(3137)
T4-09: Number of Poles
No.
Name
(Hex.)
T4-09
Number of Poles
(3138)
YASKAWA SIEPC71061737B GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets rated rotation speed (min
-1
) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated frequency (Hz) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated voltage (V) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated current (A) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated power in the units set in o1-58 [Motor Power Unit Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of motor poles.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.12 T: Auto-Tuning
Default
(Range)
0
(0, 1, 2)
Default
(Range)
-
((40 Hz to 120 Hz) × 60 × 2/
E9-08)
Default
(Range)
Determined by E9-01 and
o2-04
(40.0 - 120.0 Hz)
Default
(Range)
200 V Class: 230.0 V, 400 V:
460.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 - 510.0
V)
Default
(Range)
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Default
(Range)
Determined by E9-10
(0.10 - 650.00 HP)
Default
(Range)
Determined by E9-01
12
(2 - 48)
1005