7-2. Optional Generator Power Receptacles

Notes
OM-4434 Page 26
Y If unit does not have GFCI recep-
.
1
Combined output of all receptacles limited to
10 kVA/kW rating of the generator.
CSA/GFCI Receptacle Option
1
GFCI2 and GFCI3 supply 60 Hz single-
phase power at weld/power speed. Maxi-
mum output from GFCI-2 or GFCI-3 is 2.4
kVA/kW. Circuit breaker protection is the
same as standard receptacles.
If a ground fault is detected, the GFCI Reset
button pops out and the circuit opens to dis-
connect the faulty equipment. Check for
damaged tools, cords, plugs, etc. con-
nected to the receptacle. Press button to re-
set receptacle and resume operation.
Y Power is still present at the 240 volt
.
tacles, use GFCI-protected exten-
sion cord.
Generator power decreases as weld
current increases.
Set Fine Control R1 at 10 for full genera-
tor power.
120 V 20 A AC GFCI Receptacles
GFCI-2 and GFCI-3
receptacle when only one circuit
breaker trips.
Unplug power cord before attempt-
ing to service accessories or tools.
At least once a month, run engine at
weld/power speed and press Test but-
ton to verify GFCI is working properly.
Ref. 205 903
Work like a Pro!
Pros weld and cut
safely. Read the
safety rules at
the beginning
of this manual.