SECTION 7 − OPERATING AUXILIARY EQUIPMENT

7-1. Standard Receptacles

1
4
5
2
6
3
Y If unit does not have GFCI re-
ceptacles, use GFCI-protected
extension cord.
.
Generator power decreases as
weld current increases.
Set Fine Control R1 at 10 for full
generator power.
1
240 V 50 A AC Receptacle RC1
RC1 supplies 60 Hz single-phase
power at weld/power speed. Maxi-
mum output is 10 kVA/kW.
2
120 V 20 A AC Duplex Recep-
tacle RC2
3
120 V 20 A AC Duplex Recep-
tacle RC3
RC2 and RC3 supply 60 Hz single-
phase power at weld/power speed.
Maximum output from RC2 or RC3 is
2.4 kVA/kW.
4
Circuit Breaker CB1
CB1 protects receptacles RC1, RC2,
and RC3 from overload. If CB1
opens, the receptacles do not work.
Place switch in On position to reset
breaker.
5
Circuit Breaker CB2
6
Circuit Breaker CB3
CB2 protects RC2 and CB3 protects
RC3 from overload. If a circuit break-
er opens, the receptacle does not
work.
.
Press button to reset circuit
breaker. If breaker continues to
open,
contact
Factory
Authorized Service Agent.
Combined output of all receptacles
limited to 10 kVA/kW rating of the gen-
erator.
EXAMPLE: If 20 A is drawn from
each 120 V duplex receptacle, only
21 A is available at the 240V
receptacle:
2 x (120 V x 20 A) + (240 V x 21 A) =
10 kVA/kW
803 750 / Ref. 218 646-A
OM-4434 Page 25