HP Jet Fusion 340 Product Documentation Site Preparation Manual page 18

Hide thumbs Also See for Jet Fusion 340:
Table of Contents

Advertisement

Configuration 1: Single-circuit (two power wires plus protective earth)
Power specifications, model M2K88A (Regulatory Model Number: VCVRA-1804)
Dedicated line
Number of power wires
Input voltage
Input frequency
Maximum power consumption
Maximum load current
Branch circuit breaker (required)
Copper wire, minimum cross-sectional area
Power wire terminals
Protective Earth (PE) terminal
Power wires can be L1 & L2 or L & N, depending on the country.
1
This product has been evaluated to ±10% of the rated nominal voltage range (200–240 V) to allow for line fluctuation.
2
If the wire is more than 4.5 m (15 ft) long, HP recommends increasing the wire gauge appropriately.
3
WARNING!
incorporated in the equipment (5 kA rated interrupting capacity).
Power specifications, model M2K85A and M2K86A (Regulatory Model Number: VCVRA-1804)
Dedicated line
Number of power wires
Input voltage
Input frequency
Maximum power consumption
Maximum load current
Branch circuit breaker (required)
Copper wire, minimum cross-sectional area
Power wire terminals
Protective Earth (PE) terminal
Power wires can be L1 & L2 or L & N, depending on the country.
1
This product has been evaluated to ±10% of the rated nominal voltage range (200–240 V) to allow for line fluctuation.
2
If the wire is more than 4.5 m (15 ft) long, HP recommends increasing the wire gauge appropriately.
3
14
Chapter 4 Plan the printer production area and environment
Ensure that mains fault current is compatible with proper operation of the protection devices
Yes
2 + Protective Earth (PE) wire
1
200–240 V
2
50/60 Hz
6300 W
36 A (200–220 V)
32 A (221–240 V)
2 poles, 32, 40, or 50 A (Europe)
2 poles, 50 A (rest of the world)
6 mm² (10 AWG) with a 32 A circuit breaker
10 mm² (8 AWG) with a 40 or 50 A circuit breaker
Straight wire to terminal block
Straight wire with ferrule to ground block
Yes
2 + Protective Earth (PE) wire
1
200–240 V
2
50/60 Hz
6300 W
36 A (200–220 V)
32 A (221–240 V)
2 poles, 32, 40, or 50 A (Europe)
2 poles, 50 A (rest of the world)
6 mm² (10 AWG) with a 32 A circuit breaker
10 mm² (8 AWG) with a 40 or 50 A circuit breaker
Straight wire to terminal block
Straight wire with ferrule to ground block
3
3
3
3
ENWW