6.5 Function setting

Function setting list
Function
Function name
No.
1: Filter maintenance
indicator
1
2: Fan power increase
5
Power recovery mode
Outdoor temperature
36
indication
Indoor temperature
37
indication
Supply air (calculated
38
value) temperature
indication
Correction of
39
temperature exchange
efficiency (tens digit)
Correction of
40
temperature exchange
efficiency (ones digit)
Correction of outdoor
41
temperature
Correction of indoor
42
temperature
Function setting value
[0]
[1]
[2]
[3]
1: Yes
1: No
1: Yes
2: No
2: No
2: Yes
Auto-
matic
Stop
Run
recov-
ery
Hide Show
Hide Show
Hide Show
Function setting value: 0 to 9
Temperature exchange efficiency (tens digit): 0 to 9
Function setting value: 0 to 9
Temperature exchange efficiency (ones digit): 0 to 9
Function setting value: 0 to 14
Correction of outdoor temperature: -7°C to 7°C (1°C intervals)
Function setting value: 0 to 14
Correction of indoor temperature: -7°C to 7°C (1°C intervals)
[4]
[5]
[6]
[7]
[8] [9]
— —
— —
— —
— —
— —
Eng-45
Factory
default
Function description
setting
1: Set the filter maintenance indica-
tion to show/hide.
2: Set Use/No use of the function
that increases the fan output
1
every 1/3 of 6.4.11 Maintenance
interval passes.
- This function cannot be used
when the fan output is set to the
highest (100%).
Set the operation mode when the
power is recovered after the product
stopped.
[1] Stop:
The operation mode becomes stop.
[2] Run:
3
The operation mode becomes run-
ning.
[3] Automatic recovery:
The operation mode becomes the
mode that was set before the power
failure.
Set to show/hide the temperature
detected by the built-in thermistors.
0
Set the settings of 6.4.2.4 also.
No.36:
LO is displayed when lower than 2°C
0
and HI is displayed when 36°C or
higher.
No.37:
LO is displayed when lower than 9°C
and HI is displayed when 37°C or
higher.
No.38:
This is the same as No.37.
Note
0
If both function settings No. 38 and
84 are [1], only the function set-
ting No. 84: CO
concentration is
2
displayed on the «Main display»
screen. (Since the same display
position is allocated, the priority is
given to the indication of function
setting No.84: CO
concentration.)
2
Set the value of temperature
8
exchange efficiency used for the
calculated value of No.38 Supply air
temperature indication.
5
Factory default setting: 85%
When No.36 Outdoor temperature
indication and No.37 Indoor temper-
7
ature indication are set to Show, set
the correction value of the tempera-
ture shown on the controller.
Example: If the temperature
detected by the built-in thermistor
is 20°C and the correction value is
+3°C (the function setting value is
10), the temperature indicated by the
controller will be 23°C.
7
Note
- The indication value is not cor-
rected when Lo or Hi.
- Correction values are not reflected
to the control (such as «Auto by-
pass») using outdoor/indoor tem-
peratures.