5.2 External device connection use

Connect the each cable for external devices to the control
circuit board according to the way below.
1) Remove 2 screws. Pull the control box. (It stops in the
middle)
2) Remove an insulating sheet. (Be careful of the protrusions
on both sides of the control box)
Insulating sheet
3) Connect the cables.
TM3
TM4
TB5
TM2
CN 105: IT interconnection Wi-Fi
TM200 1(+,–): Analog input 1 for Sensor 0-10V
2(+,–): Analog input 2 for Sensor 0-10V
TM201 1-2: Volt-free contact for bypass switch
3-4: Volt-free contact for boost switch
TM2: Slim-Lossnay connection cable
TM3: Signal output
(Pre-heater, Malfunction, Operation monitor)
TM4: Operation of the remote controller
Please use P-RCC-E (Optional cable)
TB5: Not in use
Controll box
Screw
Protrusion
Controll box
TM201
TM200
CN105
4) Make a cut in the Bush. Then pass the cord of the external
device through the Bush.
Attach the insulating sheet on the control box.
Insert the control box to the product, attach it with two
screws. (Don't forget to place the insulating sheet)
Bind the external device wirings with a cable strap
(Included) and attach it under the product. (It is
recommended to install it with flexibility so that it will not be
loaded from the outside.)
Insert the cutting
Eng-21
Bush
Controll box
Screw
Cable strap