 Installation position of Shut-off valve unit in case of recovery by pump down
◆ Ceiling mounted type (include Duct type)
Total connectable pipe length to the downstream side
Minimum
of Shut-off Valve unit [m]
floor area
A
Total capacity of indoor units on the downstream side
min
of Shut-off Valve unit [HP]
2
[m
]
1 HP*
2 HP
5
6
7
9.6
4.6
8
23.7
18.8
9
37.9
32.9
10
52.1
47.1
11
66.3
61.3
12
80.5
75.5
13
94.6
89.7
14
108.8
103.8
15
123.0
118.0
16
137.2
132.2
17
151.3
146.4
18
165.5
160.5
19
179.7
174.7
20
193.9
188.9
21
208.1
203.1
22
222.2
217.3
23
236.4
231.4
24
250.6
245.6
25
264.8
259.8
26
278.9
274.0
27
293.1
288.1
28
300.0
300.0
29
300.0
300.0
30
300.0
300.0
31
300.0
300.0
32
300.0
300.0
33
300.0
300.0
34
300.0
300.0
35
300.0
300.0
36
300.0
300.0
37-110
300.0
300.0
* Including less than 1HP
 Individual shut-off (Set up the indoor DN CODE No. [107] to 2)
The allowable installation position differs depending on
the length of the total connecting pipe.
◆ The total connection pipe length on the downstream side of Shut-off Valve unit is 10m.
10
Installation
8
not permitted
6
4
2
0
5
20
35
Minimum floor area A
Ceiling mounted type (include Duct type)
3 HP
4 HP
5 HP
6 HP
13.8
8.8
3.8
28.0
23.0
18.0
13.0
42.1
37.1
32.2
27.2
56.3
51.3
46.3
41.4
70.5
65.5
60.5
55.5
84.7
79.7
74.7
69.7
98.8
93.9
88.9
83.9
113.0
108.0
103.0
98.1
127.2
122.2
117.2
112.2
141.4
136.4
131.4
126.4
155.6
150.6
145.6
140.6
169.7
164.7
159.8
154.8
183.9
178.9
173.9
169.0
198.1
193.1
188.1
183.1
212.3
207.3
202.3
197.3
226.4
221.5
216.5
211.5
240.6
235.6
230.6
225.7
254.8
249.8
244.8
239.8
269.0
264.0
259.0
254.0
283.2
278.2
273.2
268.2
297.3
292.3
287.4
282.4
300.0
300.0
300.0
296.6
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
Installation permitted
50
65
80
95
2
[m
]
min
◆ Wall mount and under ceiling type
Total connectable pipe length to the downstream side
Minimum
floor area
A
Total capacity of indoor units on the downstream side
min
2
[m
]
7.8 HP
1 HP*
5
6
7
8
3.1
4.0
9
14.7
18.2
10
26.3
32.4
11
37.9
46.6
12
49.5
60.7
13
61.1
74.9
14
72.7
89.1
15
84.3
103.3
16
95.9
117.4
17
107.5
131.6
18
119.1
145.8
19
130.7
160.0
20
142.3
174.2
21
153.9
188.3
22
165.5
202.5
23
177.1
216.7
24
188.7
230.9
25
200.3
245.0
26
211.9
259.2
27
223.5
273.4
28
235.1
287.6
29
246.7
300.0
30
258.3
300.0
31
269.9
300.0
32
281.5
300.0
33
293.1
300.0
34
300.0
300.0
35
300.0
300.0
36
300.0
300.0
37-110
300.0
* Including less than 1HP
10
Installation
8
not permitted
6
4
2
0
110
5
20
122
of Shut-off Valve unit [m]
of Shut-off Valve unit [HP]
2 HP
3 HP
4 HP
5 HP
9.7
4.8
21.3
16.4
11.4
6.4
32.9
28.0
23.0
18.0
44.5
39.6
34.6
29.6
56.1
51.2
46.2
41.2
67.7
62.8
57.8
52.8
79.3
74.4
69.4
64.4
90.9
86.0
81.0
76.0
102.5
97.6
92.6
87.6
114.1
109.2
104.2
99.2
125.7
120.8
115.8
110.8
137.3
132.4
127.4
122.4
148.9
144.0
139.0
134.0
160.5
155.6
150.6
145.6
172.1
167.2
162.2
157.2
183.7
178.8
173.8
168.8
195.3
190.4
185.4
180.4
206.9
202.0
197.0
192.0
218.5
213.6
208.6
203.6
230.1
225.2
220.2
215.2
241.7
236.8
231.8
226.8
253.3
248.4
243.4
238.4
264.9
260.0
255.0
250.0
276.5
271.6
266.6
261.6
288.1
283.2
278.2
273.2
299.7
294.8
289.8
284.8
300.0
300.0
300.0
296.4
300.0
300.0
300.0
300.0
300.0
300.0
300.0
300.0
Installation permitted
35
50
65
80
2
Minimum floor area A
[m
]
min
Wall mount and under ceiling type
6 HP
7.8 HP
1.4
13.0
4.0
24.6
15.6
36.2
27.2
47.8
38.8
59.4
50.4
71.0
62.0
82.6
73.6
94.2
85.2
105.8
96.8
117.4
108.4
129.0
120.0
140.6
131.6
152.2
143.2
163.8
154.8
175.4
166.4
187.0
178.0
198.6
189.6
210.2
201.2
221.8
212.8
233.4
224.4
245.0
236.0
256.6
247.6
268.2
259.2
279.8
270.8
291.4
282.4
300.0
294.0
300.0
300.0
95
110