Toshiba MCY-MUG0401HSW-E Service Manual page 244

Hide thumbs Also See for MCY-MUG0401HSW-E:
Table of Contents

Advertisement

No.
Part
Work procedure
2. Attachment
1)Fix the control P.C. board to the card edge
spacers. (4 places)
2)Connect the connectors disconnected in item
1-2) as before.
For connectors, check there is no missing
or contact failure. The lead wire should be
wired so as not to touch the cement
resistance R03.
3)DIP switch SW01 and SW03 should be set
according to the table below.
Settings vary depending on the model and
whether or not the Battery kit is connected to
CN521.
▼ If the Battery kit (CN521) is not connected. (Factory setting)
RBM-***
Setting of SW01
ON
SV1121HUPE
OFF
ON
SV1801HUPE
OFF
▼ If the Battery kit (CN521) is connected.
RBM-***
Setting of SW01
ON
SV1121HUPE
OFF
ON
SV1801HUPE
OFF
4)Attach the electrical control box cover.
(Refer to 1. of 2 Attachment)
Setting of SW03
SW01
SW03
ON
OFF
1 2 3 4
1 2 3 4
SW01
SW03
ON
OFF
1 2 3 4
1 2 3 4
Setting of SW03
SW01
SW03
ON
OFF
1 2 3 4
1 2 3 4
SW01
SW03
ON
OFF
1 2 3 4
1 2 3 4
243
Remarks
R03
Lead wire
CN521
SW01
SW03

Advertisement

Table of Contents
loading